Approved Vent; Approved Terminations; Vent Installation - Lopi 864 TV 40K CleanFace Installation Manual

Direct vent fireplace
Table of Contents

Advertisement

Finalizing the Installation

Approved Vent

Vertical terminations must use the 8" (203mm) to 6-5/8" (168mm) reducer (Travis part # 98900165) to
the fireplace.
Horizontal terminations must use 8" (203mm) diameter Dura-Vent Direct-Vent Pro (or GS)*.
Installation instructions for Dura-Vent may be found at
* Other vent may be approved with this fireplace. Check with the vent manufacturer for details.

Approved Terminations

Vertical terminations must use the high-wind termination (46DVA-VCH or 58DVA-VCH)
Horizontal terminations must use the high-wind termination (58DVA-HC) – do not use the high-wind
sconce cap.

Vent Installation

Slide the vent sections together and turn 1/4 turn until the sections lock in
place.
Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.
Horizontal sections require a 1/4" (6mm) rise every 12" (305mm) of travel
Horizontal sections require non-combustible support every three feet (e.g.:
plumbing tape)
Vent termination must not be located where it can become plugged by snow
or other material.
Use the vinyl siding standoff when installing on a structure with vinyl siding.
Venting termination shall not be recessed into a wall or siding.
© Travis Industries
(for qualified installers only)
6-5/8" (168mm) Diameter Vent
Reducer - # 98900165
www.duravent.com
1/29/2020 - 1499
21
864 40K CF Install Aust