Case Study - Pressure Sensor Open/Short - Samsung AM072BXV Series Service Manual

System air conditioner outdoor unit
Table of Contents

Advertisement

Troubleshooting
4-4 Case study for trouble shoots (cont.)
4-4-17 Case study – Pressure sensor open/short
▪ Disconnection or breakdown of relevant sensor.
- E291 : High pressure sensor error
- E296 : Low pressure sensor error
Check sensor connector
problem?
Refrigerant amount
insufficient
voltage between
Pressure pins 3&4 on PBA = 5V
Replace PBA
Samsung Electronics
No
No
No
Yes
Yes
Yes
Fix
Fix
Replace sensor
175