Troubleshooting
4-4 Case study for trouble shoots (cont.)
4-4-13 Case study – Poor cooling caused by IPM overheated
- Problem : Poor cooling
- Condition : Compressor frequency doesn't increase, IPM temperature is too high, Low pressure is high
- History
: 13.05.07 Trial operation
: 13.05.27 Inverter PBA, EMI PBA, Reactor replacement
: 13.05.27 IPM temperature ↑ → comp Hz ↓ → cooling capacity ↓
Test
Upper PBA
(inv 2)
Lower PBA
(inv 1)
- Root cause : Bad contact of IPM cause by faulty bolt.
IPM
Heat sink
- Conclusion : Change bolt to new one, reattach the IPM → Problem solved
Date
OD Temp
High pressure
Low pressure
Comp1
Comp2
Current1
Current2
IPM1
IPM2
※ IPM Temp Protection
- Hz Hold : 90℃
- Hz Down : 93℃
Samsung Electronics
5/27
case 1
upper PBA change
PBA_A
PBA C
freq. 55hz
freq. 54hz
IPM 89℃
IPM 82℃
PBA B
PBA B
freq. 52hz
freq.51hz
IPM 86℃
IPM 92℃
IPM1
5/28
5/29
38
38
30.5
30.4
10.9
11.4
52
52
55
55
12.3
15.3
10.3
14.2
86
89
89
81
Basic
Reattach #1
5/28
case 2
lower PBA change
PBA C
freq. 55hz
IPM 79℃
CB D
freq. 52hz
IPM 91℃
IPM2
There is no thermal grease.
Date
6/5
OD Temp
41.6
High pressure
34.7
Low pressure
10.5
Comp1
61
Comp2
64
Current1
14.9
Current2
14.2
IPM1
88
IPM2
90
Reattach #2
※ HP Protection
- Hz Hold : 36 kgf/㎠
- Hz Down : 37 kgf/㎠
case 3
exchange PBA position each other
PBA D
freq. 55hz
IPM 81℃
PBA C
freq. 52hz
IPM 89℃
IPM 2- Reattach
6/5
40.8
36.4
9.9
82
85
20.2
19.3
85
86
Solved