Samsung AM072BXV Series Service Manual page 243

System air conditioner outdoor unit
Table of Contents

Advertisement

Piping Diagram
7-3 Functions (cont.)
7-3-2 Control (cont.)
7-3-2-3 Normal operation modes (cont.)
Heating operation
▪ Purpose
Enable heating in the entire target space.
▪ Control specifications in detail
Actuator
Compressor
Outdoor Fan Motor
Electronic Expansion Valve – Main (Main EEV)
Electronic Expansion Valve – EVI (EVI EEV)
Solenoid Valve - 4way
Solenoid Valve – EVI Bypass
Solenoid Valve – EVI
Solenoid Valve – Hot Gas Bypass
Solenoid Valve – Accumulator Oil Return
Solenoid Valve – Hot Gas Bypass 2 (HR Only)
Solenoid Valve – Main EEV (HR Only)
Solenoid Valve – Main Cooling (HR Only)
Samsung Electronics
Abbrev.
-
Operation
COMP
Range
Operation
OFM
Range
Operation
E_M
Range
Operation
E_EVI
Range
V_4W
Operation
V_EB
Operation
V_EVI
Operation
V_HG
Operation
V_AR
Operation
V_HG2
Operation
V_ME
Operation
V_MC
Operation
Normal Cooling
Target low pressure control
(default : 8kgf/cm2,g)
14~140Hz
Target high pressure control
(default : 25kgf/cm2,g)
0-39step (0-1300rpm)
Full Open
2000step
*Subcooling control
(default: SC 20 K)
0-480step
Off
On (Open): *T_a > 38℃ or 50Hz ↓
Off (Close): T_a < 36℃↓ and 70Hz ↑
On (Open)
Off (Close)
On (Open)
On (Open)
On (Open)
Off (Close)
237