Case Study - E108, E604, E613 - Samsung AM072BXV Series Service Manual

System air conditioner outdoor unit
Table of Contents

Advertisement

Troubleshooting
4-4 Case study for trouble shoots (cont.)
4-4-9 Case study – E108, E604, E613
PIM display
Contents
Communication error between wired remote controller & Indoor unit
Error result
Remote controller stop
- When tracking between wired remote controller and
indoor unit/ventilator (ERV) is not complete for more than
3 minutes( ex: System communication error like E201, E108...)
Cause
- IDU address has been changed after wired remote controller
tracking completion
1) Power reset of Wired Remote controller
Treatment
(Manual reset ; re connect the power wire)
PIM display
Contents
Error which occurs when there is no communication between DMS and PIM/SIM for 15 minutes
Error result
PIM stop
- System communication error like E201, E108...
Cause
- Wired disconnection
- System communication error fix
Treatment
- Check the wire
Error code
Comm. error between
E613
Address duplication of IDU/MCU/EEV
E108
Tracking error between remote control-
E604
Samsung Electronics
E604
Description
DMS and PIM/SIM
kit
ler and the IDU
E613
Cause
Comm. was not finished
Because of E108
EEV KIT address setting
Failure (human error)
Tracking fail because of E108
Solution
Fix E108
Fix IDU address
Power reset on
Wired remote controller
163