Troubleshooting
4-3 Appropriate Measures for Different Symptom (cont.)
■ IPM breakdown diagnostics (FAN PBA)
1. Preparations before checking
1) Power Off
2) IPM failure, discharge mode may not work properly. Therefore, wait more than 15 minutes after the Power Off.
3) Remove all of the Fan PBA connectors. ((FAN motor connector included.)
4) Prepare the digital multi tester.
2. Inspection Method
1) Refer to Figure1 and Table1, respectively the resistance value and diode voltage value measure.
2) According to the criterion in Table 1 to determine whether the failure of IPM.
Division
Measure
the resistance values
Measure the diode
voltage values
Samsung Electronics
Measured Point
Criterion
+
-
40
U
40
V
40
W
More than 500 ㏀
U
34
V
34
W
34
U
40
V
40
W
40
0.3~0.7V
34
U
34
V
34
W
Measurement error can occur for reasons such as the ini-
tial measurement condenser discharge.
Measured over at least three times.
< Table 1 >
Remark
123