Samsung AM072BXV Series Service Manual page 277

System air conditioner outdoor unit
Table of Contents

Advertisement

Piping Diagram
7-3 Functions (cont.)
7-3-3 Others (cont.)
7-3-3-1 Field Setting (cont.)
Cooling capacity correction
▪ Purpose
Control the cooling performance.
▪ Concept
The Target Evap In temperature is changed to control the low pressure in cooling mode.
▪ Control specifications in detail
- The target low pressure for outdoor units and the compressor operation frequency are controlled according
to the Target Evap In Temp. that was configured in cooling mode.
- See "Compressor capacity control" for details on compressor operation specifications.
Input unit
Seg1
Main
0
▪ Notes
- The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compressor.
- Error E560 will be triggered if all the compressors on outdoor units are disabled.
(The SVC V/V must be closed for outdoor units if modules are installed and all the compressors on a single
outdoor unit are disabled.)
Samsung Electronics
Seg2
Seg3
0
0
0
1
0
0
0
0
Seg4
0
1
2
3
4
5
6
Temperature(℃ )
7-9
5 - 7 (default)
9 - 11
10 - 12
11 - 13
12 - 14
13 - 15