Piping Diagram
7-3 Functions (cont.)
7-3-3 Others (cont.)
7-3-3-1 Field Setting (cont.)
Temperature to trigger defrost operatio
▪ Purpose
Prevent excessive frost formation in a high-humidity condition.
(Apply setting when the product is being installed in a humid area such as near a river or lake.)
▪ Concept
Defrost operation is performed frequently if there is frost formation on heat exchangers in heating mode.
▪ Control specifications in detail
- Defrost operation is performed if the amount of frost that formed is smaller than the option setting when the heat
exchangers are checked for frost formation based on the difference between the outdoor temperature and heat
exchanger temperature (Cond out, Suction)
- See "Defrost control" for details on defrost operation specifications.
Input unit
Seg1
Main
0
▪ Notes
- If this option is configured and the units are in a very humid location, heating performance may degrade due
to frequent defrost operation.
Samsung Electronics
Seg2
Seg3
0
5
0
Option is
configured
Seg4
Temperature to trigger defrost operation
0
Apply setting when the product is installed in a humid
1
area such as near river or lake
Option is not
configured
Standard (default)
Amount of frost
formed
Cond out, Suction
Time