Change The Device Name - Banner DXM1200-Bx Instruction Manual

Wireless controller
Hide thumbs Also See for DXM1200-Bx:
Table of Contents

Advertisement

®
PROFINET
16. Click Apply.
S
R
:
The IP address for the device is updated.
TEP
ESULT
17. Click Assign IP address to complete the step.
S
R
:
This step is completed for every device.
TEP
ESULT
A
C
T
T
FTER
OMPLETING
HIS
ASK
By default, each DXM shipped from the factory is assigned the IP address 192.168.0.1.
Immediately after the PROFINET protocol is enabled, the DXM has an IP address of 0.0.0.0. We recommend using the TIA Portal to give the
DXM an IP address so that the address is saved in the unit. When the PLC powers up, this IP address is accessible. The PLC can change the
IP address if it is configured to do so.
If the PLC assigns the DXM IP address (for example, using the Set IP address in the project option in Siemens TIA Portal), the DXM receives
the specified address, but only after the program has been loaded into the PLC and is running. If the DXM is restarted after it was discovered
and configured by the PLC, the DXM retains the IP address that was assigned to it using the LCD or software until after the PLC discovers the
DXM and assigns it the specified address again. However, if this address is different than what is specified in the PLC, the DXM reverts to the
address specified in the PLC after the PLC becomes active again.
These configuration options conform to the PROFINET standard.

9.5.3. Change the Device Name

Follow these instructions to change the name of the DXM using the Siemens TIA Portal (v14) software. Use these instructions as a basis if you
are using another controller (PLC).
1.
Open a project and click on Devices & networks.
S
R
:
The Network view displays.
TEP
ESULT
2.
Right-click on the DXM icon and select Assign device name.
S
R
:
The Assign PROFINET device name window displays. The software searches for devices of the same type.
TEP
ESULT
Enter the desired name in the PROFINET device name field. Note that each name can be used only once.
3.
4.
Click Assign name.
S
R
:
The device now has a PROFINET name.
TEP
ESULT
54
:
© Banner Engineering Corp. www.bannerengineering.com