Installation Procedure

Step 17. Optional : Setting the Emergency Temperature Output (ETO) function

CAUTION
In order to deploy the ETO function, the MIM-B14, an external contact interface module, must be installed in each
indoor unit.
The ETO is a concept of emergency operation of indoor units. If the indoor unit 1 (main indoor unit) stops because of
an error, the indoor unit 2 (sub indoor unit) starts to operate.
Basically, the indoor unit 2 operates in the previous mode. [For the first time operation, it starts in 24 °C Auto
mode.]
To set more detailed operation conditions for the indoor unit 2, use the S-net Pro.
Emergency Temperature Output (ETO) function
Communication between
indoor and outdoor units (F1
and F2)
1
Main indoor unit
Disable the external contact control (Default).
Connect the S-net pro2 to F1 and F2.
Enable the ETO function and set the temperature and time.
2
Sub indoor unit
(Required) Enable the external contact control (with the installation option SEG14 - Reverse Control).
Connect the S-net pro2 to F1 and F2.
Enable the entrance control and set the mode, set temperature, and fan speed.
[Main]
38
English
Main indoor unit
External contact interface
Sub indoor unit
[Sub]
Error output
port (1, 2)
module MIM-B14
Contact input
port (5, 6)