Installation Procedure
NOTE
•
Insert the power and the communication cables to the
cable insert hole, then arrange and connect the cables,
as shown in the figure:
Cable insert
hole
Power cable
Indoor power supply
Power supply
Max/Min(V)
220 to 240V, 50 Hz
Communication cable
0.75 mm², 2 wires
20
English
Communication
cable
Indoor power cable
±10%
AC power: M4 screw
13
11
Tightening torque (kgf • cm)
M3.5
M4
•
1 N·m = 10 kgf·cm
•
Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)
•
Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
•
When installing the indoor unit in a computer room or
network room, use the double shielded communication
FROHH2R or LiYCY type.
(Unit: mm)
Communication: M3.5 screw
9.0
7.5
8.0 to 12.0
12.0 to 18.0