Installation Procedure
CAUTION
Comply with the length and height limits described in
the figure above.
For the product that uses the R-32 refrigerant, Install
the indoor unit on the wall 1.8 m or higher from the
floor.
The indoor unit must be installed according to the
specified distances in order to permit accessibility from
each side, to guarantee correct operation, maintenance,
and repair of the unit.
The components of the indoor unit must be reachable
and removable under safe conditions for people and
the unit.
Do not carry the unit by holding the refrigerant or drain
pipes to avoid product damage.
Carry the unit by holding the hanger plates located on
the corners of the unit.
Step 3 Optional: Insulating the body of
the indoor unit
If you install a cassette type indoor unit on the ceiling when
temperature is over 27°C and humidity is over 80%, you must
apply an extra 10 mm thick polyethylene insulation or a similar
type of insulation to the body of the indoor unit.
Cut away the part where pipes are pulled out for the insulating
work.
10
English
Insulate the end of the pipe and some curved area by using
separate insulator.
NOTE
A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit, use A as
the reference for its outer circumference.)
Indoor unit type and models
360 cassette type <S>
(947 x 947 x 281)
(947 x 947 x 365)

Step 4 Installing the indoor unit

When deciding on the location of the air conditioner the
following restrictions must be taken into account.
1
Determine the positions of the pipe and the drain hose
hole as shown in the pattern sheet, and drill the hole with
an inner diameter of 14 mm.
NOTE
Since the diagram is made of paper, it may shrink or
stretch slightly due to temperature or humidity. For this
reason, before drilling the holes, be sure to maintain
the correct dimensions between the markings.
A
(Unit: mm)
Dimensions
AC052BN6PKG
2610 x 130
AC071BN6PKG
AC100BN6PKG
2610 x 215
AC120BN6PKG
AC140BN6PKG