Installation Procedure
Option
SEG 19
SEG 20
Individual control
Function
Page
with remote
Indication Details Indication Details Indication
0, 1
2
Indication
and
3
details
3
4
By SEG4 setting, Minimizing fan operation when thermostat is off.
Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
Fan stops or operates Ultra low in Cooling when thermostat is off.
Even if you set the Use of drain pump option to 0, it is automatically set to 2 (the drain pump is used with 3 minute delay).
Example: When installing DPM (1 Outdoor unit with 4 indoor units)
Condition
External control
Default
Disuse
Use (Indoor 3)
Use (Indoor 4)
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
Soft Off: The indoor unit turns off its operation at the indicated time in the table for Installation Option after its final motion
detection. But, it turns on again if the MDS detects motion.
Hard Off: Designated time after SOFT OFF, it cannot turn on automatically when it detects motion. Users should control to
turn on the indoor unit with remote control, etc.
36
English
SEG 21
SEG 22
Heating setting
Details
Indoor 1
0
Default
Indoor 2
Reserved
1
Indoor 3
2
Indoor 4
Level control
Indoor 1
Use
4
Disuse
Not set (0)
Use
Not set (0)
SEG 23
Indication
0
1
Standard
2
3
4
Premium
5
6
7
Off after 20 min. (Soft Off only)
Standard
8
Off after 40 min. (Soft Off only)
9
Off after 80 min. (Soft Off only)
A
Off after 20 min. (Soft Off only)
Premium
B
Off after 40 min. (Soft Off only)
C
Off after 80 min. (Soft Off only)
SEG14 Setting
Indoor 2
Indoor 3
Not set (0)
Not set (0)
Not set (0)
Not set (0)
1~3
Not set (0)
Not set (0)
SEG 24
Cycle time of swing
Details
Indication
Details
0
34 seconds (default)
1
30seconds
2
38 seconds
Result
Indoor 4
Slave (All)
Master (Indoor 1),
Not set (0)
Slave (Indoor 2,3,4)
Not set (0)
Slave (All)
Master (Indoor 4),
5~7
Slave (Indoor 1,2,3)

Advertisement