7.3
With PROFIBUS PA / with FOUNDATION Fieldbus
7.3.1
Electrical data
Note
Pressure sensor module
The following electrical data also apply to electronics with pressure sensor module.
Auxiliary power supply bus cir‐
cuit (terminals 6 and 7)
Bus voltage
For connecting to circuits with
the following peak values
•
Bus connector with FISCO
supply unit
•
Bus connector with barrier
Effective inner capacitance C
Effective inner inductance L
Current consumption
Additional fault current
Safety shutdown can be acti‐
vated using "Jumper" (termi‐
nals 81 and 82)
•
Input resistance
•
Signal status "0" (shutdown
active)
•
Signal status "1" (shutdown
not active)
SIPART PS2 (6DR5...)
Compact Operating Instructions, 11/2022, A5E03436620-AG
Basic device
without explosion
protection
9 ... 32 V
-
-
i
-
i
Electrically isolated from bus circuit and digital input
7.3 With PROFIBUS PA / with FOUNDATION Fieldbus
Basic device with
Basic device with
explosion protec‐
explosion protec‐
tion Ex "db"
tion Ex "ia", Ex "db ia"
Bus-powered
9 ... 32 V
9 ... 24 V
Umax ≤ 35 V
U
≤ 17.5 V
i
Pmax ≤ 2.5 W
I
≤ 380 mA
i
P
≤ 5.32 W
i
Umax ≤ 35 V
U
≤ 24 V
i
Pmax ≤ 2.5 W
I
≤ 250 mA
i
P
≤ 1.2 W
i
-
Negligible
-
8 μH
11.5 mA ± 10 %
0 mA
> 20 kΩ
0 ... 4.5 V or unused
13 ... 30 V
Technical data
Basic device with
explosion protec‐
tion Ex "ic", "ec", "tb"
9 ... 32 V
"ic":
U
≤ 17.5 V
i
I
≤ 570 mA
i
"ec"/"tb":
U
≤ 32 V
n
"ic":
U
≤ 32 V
i
"ec"/"tb":
U
≤ 30 V
n
I
≤100 mA
n
Negligible
"ic":
8 μH
67