With Profibus Pa / With Foundation Fieldbus; Electrical Data - Siemens SIPART PS2 Operating Instructions Manual

Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

7.3

With PROFIBUS PA / with FOUNDATION Fieldbus

7.3.1

Electrical data

Note
Pressure sensor module
The following electrical data also apply to electronics with pressure sensor module.
 
Auxiliary power supply bus cir‐
cuit (terminals 6 and 7)
Bus voltage
For connecting to circuits with
the following peak values
Bus connector with FISCO
supply unit
Bus connector with barrier
Effective inner capacitance C
Effective inner inductance L
Current consumption
Additional fault current
Safety shutdown can be acti‐
vated using "Jumper" (termi‐
nals 81 and 82)
Input resistance
Signal status "0" (shutdown
active)
Signal status "1" (shutdown
not active)
SIPART PS2 (6DR5...)
Compact Operating Instructions, 11/2022, A5E03436620-AG
Basic device
without explosion
protection
9 ... 32 V
 
-
 
-
i
-
i
Electrically isolated from bus circuit and digital input
7.3 With PROFIBUS PA / with FOUNDATION Fieldbus
Basic device with
Basic device with
explosion protec‐
explosion protec‐
tion Ex "db"
tion Ex "ia", Ex "db ia"
Bus-powered
9 ... 32 V
9 ... 24 V
 
 
Umax ≤ 35 V
U
 ≤ 17.5 V
i
Pmax ≤ 2.5 W
I
 ≤ 380 mA
i
P
 ≤ 5.32 W
i
Umax ≤ 35 V
U
 ≤ 24 V
i
Pmax ≤ 2.5 W
I
 ≤ 250 mA
i
P
 ≤ 1.2 W
i
-
Negligible
-
8 μH
11.5 mA ± 10 %
0 mA
 
> 20 kΩ
0 ... 4.5 V or unused
13 ... 30 V
Technical data
Basic device with
explosion protec‐
tion Ex "ic", "ec", "tb"
9 ... 32 V
 
"ic":
U
 ≤ 17.5 V
i
I
 ≤ 570 mA
i
"ec"/"tb":
U
 ≤ 32 V
n
"ic":
U
 ≤ 32 V
i
"ec"/"tb":
U
 ≤ 30 V
n
I
 ≤100 mA
n
Negligible
"ic":
8 μH
67

Advertisement

Table of Contents
loading

Table of Contents