Offset/Gain Settings - Mitsubishi MELSEC-Q Q62DAN User Manual

Digital-analog converter module
Hide thumbs Also See for MELSEC-Q Q62DAN:
Table of Contents

Advertisement

4 SETUP AND PROCEDURES BEFORE OPERATION

4.6 Offset/Gain Settings

Start
3)
Switch to the offset/gain
setting mode.
1
Verify that the mode is set
to offset/gain setting and
the RUN LED is flashing.
2)
Set the offset setting
channel in buffer memory
address 22 (Un\G22).
Set buffer memory address
23 (Un\G23) to 0.
Turn the channel change
request (YB) to ON.
Verify that the channel
change completed flag
(XB) is ON.
1)
Turn the channel change
request signal (YB) to OFF.
Channel change completed
flag (XB) turns OFF.
4)
Write the adjustment amount
for the analog output value in
buffer memory address 24
(Un\G24).
4 - 12
When the user range setting is used, perform the offset and gain settings according to
the following procedure.
When the industrial shipment setting is used, offset/gain setting is not necessary.
If the utility package is installed, perform the offset/gain settings according to the
procedure described in Section 5.6.2.
(1) Offset/gain setting procedure
Turn the set value change
request signal (Y0C) ON.
Verify that X0C turns ON
after the analog output
value is changed, and then
turn the set value change
request signal (Y0C) OFF.
Set the gain setting
channel in buffer memory
address 23 (Un\G23).
Set buffer memory address
22 (Un\G22) to 0.
Turn the channel change
request signal (YB) ON.
Verify that the channel
change completed flag
(XB) turns ON.
NO
Desired analog
output value?
YES
NO
Adjust gain?
YES
1)
MELSEC-Q
4)
Adjust other
channels?
NO
Set the user range writing
request (YA) to ON, and
then register the offset/
gain settings in the D/A
converter module.
Error occurred?
NO
Switch to the normal
1
setting mode.
End
YES
2)
YES
3)
4 - 12