When User Range Setting Is Used And Initial Setting Was Made With Gx Configurator-Da; (Other System Is Available) - Mitsubishi MELSEC-Q Q62DAN User Manual

Digital-analog converter module
Hide thumbs Also See for MELSEC-Q Q62DAN:
Table of Contents

Advertisement

7 ONLINE MODULE CHANGE
MELSEC-Q

7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA

(other system is available)

(1) Conversion disable
(a)
Set D/A Conversion enable/disable (buffer memory address 0: Un\G0) for
all channel conversion disable and turn Operating condition setting request
(Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the actual analog output
value, turn OFF Operating condition setting request (Y9).
7 - 14
7 - 14