3 SPECIFICATIONS

3.4.9 Setting range (buffer memory address 20, 21: Un\G20, Un\G21)

Un\G20 (setting range CH1 to CH4)
Un\G21 (setting range CH5 to CH8)

3.4.10 Offset/gain setting mode and offset/gain specification

(buffer memory addresses 22, 23: Un\G22, Un\G23)

Un\G22 (Offset specification)
Un\G23 (Gain specification)

3.4.11 Setting value specification (buffer memory address 24: Un\G24)

3 - 29
(1) This area is used to confirm the setting range of the D/A converter module.
Settings for channels 1 to 4 are stored in Un\G20.
Settings for channels 5 to 8 are stored in Un\G21.
(2) For Q62DAN, Q62DA, b8 to b15 (CH3 and 4 information) for Un\G20 and Un\G21
(information of CH5 to CH8) are invalid.
For Q64DAN, Q64DA, Un\G21 (CH5 to CH8 information) is invalid.
b15
Output range
4 to 20 (mA)
0 to 20 (mA)
1 to 5 (V)
0 to 5 (V)
–10 to 10 (V)
User range setting
(3) 0
is default. Q68DAVN, Q68DAV is operated in 2
H
0
(default) is set for the output range setting so that 2
H
(1) Specifies the channel to be adjusted for the offset/gain settings.
(2) Specification can be made for 1 channel only.
An offset/gain setting mode error (error code 500) will occur if more than one
channel is specified at the same time.
(3) For Q62DAN, Q62DA, b2 to b7 (CH3 to CH8) are invalid.
For Q64DAN, Q64DA, b4 to b7 (CH5 to CH8) are invalid.
(4) See Section 4.6 for the details of the offset/gain settings.
b15 b14 b13 b12 b11 b10
0
0
0
0
For Q62DAN, Q62DA, b2 to b15 information is fixed at 0.
For Q64DAN, Q64DA, b4 to b15 information is fixed at 0.
(1) This area is used to set the amount of adjustment for analog output values in the
offset/gain setting mode.
(2) The valid input range is from –3000 to 3000.
When the input value is 1000, the analog output values can be adjusted by about
0.33 V for voltage output and about 0.65 mA for current output.
(3) See Section 4.6 for the details of the offset/gain settings.
b12 b11
to
to
CH4
CH3
CH8
CH7
Setting value
0
H
1
H
2
H
3
H
4
H
F
H
b9
0
0
0
0
0
0
0
0
0
0
b8
b7
b4
to
CH2
CH6
(1 to 5 V) setting even when
H
will be stored.
H
b8
b7
b6
b5
b4
0
CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1
CH8 CH7 CH6 CH5
0
CH4 CH3 CH2 CH1
MELSEC-Q
b3
b0
to
CH1
CH5
b3
b2
b1
b0
1: Channel to be set
0: Invalid
3 - 29