Figure 2 Completestat; Table 1 Controller Connections - Bard CompleteStat CS9B-THO Installation Instructions Manual

Hide thumbs Also See for CompleteStat CS9B-THO:
Table of Contents

Advertisement

Field-Installed Jumper
8403-062 Indoor Remote
Air Temperature Sensor
NOTE: Use twisted shielded pair for optional outdoor and indoor air sensors. Connect shield (drain) to 24V
common.
Terminal
D
Dehumidification
SC
24VAC to Relay Outputs D, A, W2
A
Ventilation Call
W2
2
Stage Heating
nd
W1/E
1
Stage Heating/Emergency Heat
st
SC
24VAC to Relay Outputs W1/E, Y2, Y1
Y2
2nd Stage Compressor
Y1
1st Stage Compressor
Y0
Economizer
SC
24VAC to Relay Outputs Y0, O/B, G
O/B
Reversing Valve
G
Indoor Blower
IN9
Not Used
ROS
Remote Occupancy Sensor
GND
REM
Remote Temperature Sensor
+B
Communications
-A
Communications
OAT
Outdoor Air Temperature Sensor
LAT
Leaving Air Temperature Sensor
GND
Control Ground
L
Lockout Alarm
Com
24VAC Common
24V
24VAC Hot
FIGURE 2
CompleteStat
Terminal Descriptors and Optional Inputs
TM
Field-Installed Jumper
TABLE 1
Controller Connections
Function
Field-Installed Jumper
Type
Output
24VAC
Power
Output
24VAC
Output
24VAC
Output
24VAC
Power
Output
24VAC
Output
24VAC
Output
24VAC
Power
Output
24VAC
Output
24VAC
Input
Dry Contact (Input to GND)
Input
10K Type II Thermistor
Input
10K Type II Thermistor
Input
10K Type II Thermistor
Input
Dry Contact (Input to GND)
Power
Power
8403-061 Outdoor Air
Temperature Sensor
Form
SPST Relay
SPST Relay
SPST Relay
SPST Relay
SPST Relay
SPST Relay
SPST Relay
SPST Relay
SPST Relay
Manual
2100-566F
Page
9 of 24