INSTALLATION IMPORTANT: For optimum temperature sensor 3. Route control wiring through base plate. performance, the Bard CompleteStat must be mounted 4. With the embossed “UP” arrows of the base plate on an interior wall and away from any heat sources,...
CompleteStat Setup at Time of Installation Determine the following information prior to installation. 1. Degrees Scale: °F °C 2. Unit Type: A/C 3. Options: A/C – 1H/1C 2H/2C 1H/2C 2H/1C HP – 1 Stage 2 Stage 4. Economizer: Yes 5. Fan: Off Delay (seconds) Unoccupied: Auto Occupied: Auto 6.
NOTE: Although cooling/heating setpoints can be 3. Controller will ask for password. Press UP and RIGHT accessed by simply pressing the UP or DOWN buttons to enter ‘BARD’. Press ENTER button. buttons during normal operation, any changes made in this fashion will not be permanent 4.
6. Press UP or DOWN button to choose °F 3. Press ENTER button to select/save appropriate (Fahrenheit) or °C (Celsius). Press ENTER to save economizer option. selection of scale. 4. Press LEFT button to go back to ADDITIONAL NOTE: The change from F to C will not take effect SETUP.
DEHUMIDIFICATION 3. Controller will ask for password. Press UP and RIGHT DEHUM: ENABLE buttons to enter ‘BARD’. Press ENTER button. ALLOW HEATING DEHUM: YES 4. In the TECHNICIAN menu screen, press ENTER DEHUM SETPT: 60%RH button to enter the APPLICATION menu.
(factory default). To install Bard 8403-061 Outdoor Air Temperature • Occ: “ON” = System fan will run continuously Sensor, attach the leads to terminals “OAT” and during all operational modes;...
FIGURE 10 • EMER HT = HP mode only. Dehumidification (Heat Pump) • OFF = HVAC system is inactive. • COOLING = System is in “Cooling-Only” mode. DEHUMIDIFICATION HVAC system will cycle cooling in reference DEHUM: ENABLE to cooling setpoint only. Unit will not activate ALLOW HEATING DEHUM: YES heating sequence.
Page 10
Low Temperature or High Temperature alarm. This will not affect normal operation and can be cleared easily. Bard CompleteStat should be operational at this point. For further controller enhancement or operation detail, please consult the latest edition of CompleteStat Advanced Programming &...
FIGURE 14 CompleteStat Terminal Descriptors and Optional Inputs 8403-062 Indoor Remote Air Temperature Sensor 8403-061 Outdoor Air Temperature Sensor NOTE: Use twisted shielded pair for optional outdoor and indoor air sensors. Connect shield (drain) to 24V common. TABLE 1 Controller Connections Terminal Function Type...
SEQUENCE OF OPERATION TABLE 2 Conventional 1H/1C, 2H/1C, 1H/2C or 2H/2C without Economizer Operation W1/E Fan Only Stage Cooling Stage Cooling (if employed) Stage Heating Stage Heating (if employed) Dehumidification Ventilation CS9B(E)-THOCA (CO Sensing Capability) models will activate both G and A terminals upon a ventilation call; however, the CS9B(E)-THOA (Non-CO Sensing) models will activate the A terminal only if there is an existing call for the indoor blower, whether through space conditioning or through constant fan operation.
TABLE 4 Single Stage Heat Pump without Economizer Operation W1/E Fan Only Stage Cooling Stage Heating Stage Heating Emergency Heat Dehumidification Ventilation CS9B(E)-THOCA (CO Sensing Capability) models will activate both G and A terminals upon a ventilation call; however, the CS9B(E)-THOA (Non-CO Sensing) models will activate the A terminal only if there is an existing call for the indoor blower, whether through space conditioning or through constant fan operation.
SEQUENCE OF OPERATION (CONT.) TABLE 6 Single Stage Heat Pump with Economizer Operation W1/E Fan Only Stage Cooling Stage Cooling Stage Heating Stage Heating Emergency Heat Dehumidification Ventilation CS9B(E)-THOCA (CO Sensing Capability) models will activate both G and A terminals upon a ventilation call; however, the CS9B(E)-THOA (Non-CO Sensing) models will activate the A terminal only if there is an existing call for the indoor blower, whether through space conditioning or through constant fan operation.
System Unit CompleteStat Economizer Use with Model Stages Ventilation System Control Type System Type Setting Bard Units CS9B(E)- Setting Type 1 or 2-Stage A/C w/ or THOA, THOCA 2H/2C None CRV, ERV, MFAD On/Off w/o Elec. Heat ECONWM Factory "T"...
WIRING DIAGRAMS WIRING DIAGRAM 1 Conventional 1H/1C, 1H/2C, 2H/1C or 2H/2C, with or without Dehumidification and Ventilation, No Economizer CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Wire for dehumidification units only Wire not used on MFAD ventilation option Optional wire only for 2 stage heating W**A2 units use “D”...
WIRING DIAGRAM 2 Conventional 1H/1C or 2H/1C with Honeywell W7220 Jade Control Economizer, with or without Dehumidification CompleteStat JADE Field-installed wires and jumpers Factory-installed wires and jumpers W**A2 units use “D” terminal Wire for dehumidification units only W**A1 units use “3” terminal Optional wire only for 2 stage heating For fire-smoke/emergency shutdown, remove (15kW or more)
WIRING DIAGRAMS (CONT.) WIRING DIAGRAM 3 Conventional 1H/2C or 2H/2C with Honeywell W7220 Jade Control Economizer, No Dehumidification, 2 Stage Compressor Only CompleteStat JADE Field-installed wires and jumpers Factory-installed wires and jumpers Optional wire only for 2 stage heating Field-installed wire nut (15kW or more) Remove jumper for 2 stage heat CompleteStat programmed for damper/...
WIRING DIAGRAM 5 Heat Pump 2 Stage, with or without Dehumidification and Ventilation CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Wire not used on MFAD ventilation option Wire for dehumidification units only CH*S Series heat pumps use “DH” dehumidification terminal WIRING DIAGRAM 6 Heat Pump 1 Stage with Honeywell W7220 Jade...
WIRING DIAGRAMS (CONT.) WIRING DIAGRAM 7 Heat Pump 2 Stage with Honeywell W7220 Jade Control Economizer, with or without Dehumidification CompleteStat JADE Field-installed wires and jumpers Factory-installed wires and jumpers CH*S Series heat pumps use “DH“ Wire for dehumidification units only dehumidification terminal CompleteStat programmed for damper/ Field-installed wire nut...
WIRING DIAGRAM 9 Gas/Electric 1H/2C, with or without Dehumidification and Ventilation, No Economizer CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Wire not used on MFAD ventilation option Wire for dehumidification units only W**G Series uses “A” terminal for ventilation WIRING DIAGRAM 10 I-TEC 2 Stage Heat Pump Series with No Ventilation...
WIRING DIAGRAMS (CONT.) WIRING DIAGRAM 11 I-TEC 2 Stage Heat Pump Series with CRV Ventilation Package CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Wire for dehumidification units only Wire not needed if auxiliary heat strip is 10 kW or less Manual 2100-684 Page 22 of 25...
WIRING DIAGRAM 12 I-TEC 2 Stage Heat Pump Series with ERV Ventilation Package and 8403-067 CO Detector (Fully Modulating) CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers 8403-067 to be used with non-CO Wire for dehumidification units only sensing CompleteStat Wire not needed if auxiliary heat strip is 10 kW or less Manual...
WIRING DIAGRAMS (CONT.) WIRING DIAGRAM 13 Q-TEC QA**/Q**A Series 1 Stage Air Conditioner with or without Dehumidification and Ventilation, No Economizer CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Wire for dehumidification units only Q Series with factory-installed thermostat had no terminal board and were wired directly from Plug #4. Use provided colors to wire CompleteStat.
WIRING DIAGRAM 15 QW*S Series 2 Stage Heat Pump with or without Dehumidification and Ventilation CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Wire for dehumidification units only Q Series with factory-installed thermostat had no terminal board and were wired directly from Plug #4. Use provided colors to wire CompleteStat.