*INSTALL NOTE: For optimum temperature sensor performance, the Bard CompleteStat must be mounted on an interior wall and away from any heat sources, sunlight, windows, air vents, air circulation obstructions, and/or any other cause of erratic or false temperature sensing.
3. Enter button to select Advanced and enter Advanced Screen 4. Enter button again to select/enter Applications Screen 5. Controller will ask for Admin Level Password Factory Default Admin Level Password: BARD Press Enter 6. Enter button to choose Degrees Scale (IF NECESSARY)
3. Enter button to select Advanced and enter Advanced Screen 4. Enter button again to select/enter Applications Screen 5. Controller will ask for Admin Level Password Factory Default Admin Level Password: BARD Press Enter 6. Down button through entries to highlight Additional Setup 7.
9. Enter button to save choice 10. Left button (3x) to home screen. System Enable – to enable heating / cooling from home screen, press: 1. Right button to access the Main Menu Screen 2. Down button through entries to highlight System 3.
Sequence of Operation: Conventional 1H/1C, 2H/1C, 1H/2C, or 2H/2C without Economizer Operation W1/E Fan Only Stage Cooling Stage Cooling (if employed) Stage Heating Stage Heating (if employed) Dehumidification Ventilation NOTE : CS9B(E)-THOC (CO Sensing Capability) Models will activate both G and A terminals upon a ventilation call, however the CS9B(E)-THO (NON-CO Sensing) Models will activate the A terminal only if there is an existing call for the indoor blower, whether through space conditioning, or through constant fan operation.
Sequence of Operation: Two-Stage Heat Pump, no Economizer Operation W1/E Fan Only Stage Cooling Stage Cooling Stage Heating Stage Heating Stage Heating Emergency Heat Dehumidification Ventilation NOTE : CS9B(E)-THOC (CO Sensing Capability) Models will activate both G and A terminals upon a ventilation call, however the CS9B(E)-THO (NON-CO Sensing) Models will activate the A terminal only if there is an existing call for the indoor blower, whether through space conditioning, or through constant fan operation.
Wiring Diagram Table Wiring (Note A) System Vent CompleteStat™ Economizer Use with Bard Diagram Unit Type CompleteStat™ Stages Ventilation System Control System Type Setting Units Model CS9B(E)- Setting Type 1 or 2-Stage A/C w/ THO, THOC 2H/2C None CRV, ERV, MFAD On/Off or w/o Elec.
Wiring Diagram 1: Conventional 1H/1C, 1H/2C, 2H/1C, or 2H/2C, with or without dehumidification and ventilation. CompleteStat W2 W1/E SC IN9 ROS GND REM GND L COM 24V D SC Y1 YO A+ B- OAT LAS W2 W1/E *NOTE: 2-Stage Units use HVAC System “Y1”...
Page 11
Wiring Diagram 3: Conventional 1H/1C, 2H/1C with Honeywell W7220 Jade Control Economizer, with or w/o dehum. CompleteStat W2 W1/E SC IN9 ROS GND REM GND L COM 24V D SC OAT LAS A+ B- W2 W1/E HVAC System HONEYWELL W7220 Wiring Diagram 4: Conventional 1H/2C, 2H/2C with Honeywell W7459A Control Economizer CompleteStat D SC...
Page 12
Wiring Diagram 5: Conventional 1H/2C, 2H/2C with Honeywell W7220 Jade Control Economizer CompleteStat D SC W2 W1/E SC IN9 ROS GND REM GND L COM 24V A+ B- OAT LAS PURPLE PINK W2 W1/E HVAC System HONEYWELL W7220 Wiring Diagram 6: Heat Pump 2H/1C, 3H/1C, with or without dehumidification and ventilation. CompleteStat W2 W1/E SC IN9 ROS GND REM...
Page 13
Wiring Diagram 7: Heat Pump 2-Stage, with or without dehumidification and ventilation. CompleteStat W2 W1/E SC IN9 ROS GND REM GND L COM 24V D SC Y1 YO A+ B- OAT LAT (USE ENCLOSED RELAY) 01 W2 HVAC System CRV, ERV OR MFAD Wiring Diagram 8: Heat Pump 1-Stage, with Honeywell W7459A Control Economizer, with or w/o dehum.
Page 14
Wiring Diagram 9: Heat Pump 1-Stage, with Honeywell W7220 Jade Control Economizer, with or w/o dehum. CompleteStat Wiring Diagram 10: Heat Pump 2-Stage, with Honeywell W7459A Control Economizer, with or w/o dehum. CompleteStat D SC W2 W1/E SC IN9 ROS GND REM GND L COM 24V A+ B- OAT LAT...
Page 15
Wiring Diagram 11: Heat Pump 2-Stage, with Honeywell W7220 Jade Control Economizer, with or w/o dehum. CompleteStat W2 W1/E SC IN9 ROS GND REM GND L COM 24V D SC Y1 YO A+ B- OAT LAT PURPLE PINK (USE ENCLOSED RELAY) 01 W2 HVAC System HONEYWELL...
Page 16
Wiring Diagram 13: Gas/Electric 1H/2C with or without dehumidification and ventilation package CompleteStat D SC W2 W1/E SC IN9 ROS GND REM GND L COM 24V A+ B- OAT LAT HVAC System CRV, ERV OR MFAD Wiring Diagram 14: Gas/Electric 1H/1C with Honeywell W7459A Control Economizer, with or w/o dehum. CompleteStat D SC W2 W1/E SC...
Page 17
Wiring Diagram 15: Gas/Electric 1H/2C with Honeywell W7459A Control Economizer, with or w/o dehum. CompleteStat D SC W2 W1/E SC IN9 ROS GND REM GND L COM 24V A+ B- OAT LAT HVAC System HONEYWELL W7459A Wiring Diagram 16: I-TEC 2-Stage Heat Pump Series with no ventilation package CompleteStat W2 W1/E SC IN9 ROS GND REM...
Page 18
Wiring Diagram 17: I-TEC 2-Stage Heat Pump Series with CRV ventilation package CompleteStat D SC W2 W1/E SC Y1 YO IN9 ROS GND REM GND L COM 24V A+ B- OAT LAT (USE ENCLOSED RELAY) W2 W3 Y2 B/W1 HVAC System Wiring Diagram 18: I-TEC 2-Stage HP Series with ERV ventilation package &...
Page 19
Wiring Diagram 19: Q-TEC QA**/Q**A-Series 1-Stage Air Conditioners, with or without ventilation and dehumidification CompleteStat D SC W2 W1/E SC Y1 YO IN9 ROS GND REM GND L COM 24V A+ B- OAT LAT HVAC System WHT BRN Plug #4 Wiring Diagram 20: Q-TEC QH**/Q**H Series 1-Stage Heat Pump, with or without ventilation and dehumidification CompleteStat W2 W1/E SC...
Page 20
Q-Series with factory installed thermostat had no terminal board and were wired directly from Plug#4. Use provided colors to wire CompleteStat Field-installed wires and jumpers Factory-installed wires and jumpers Bard CompleteStat should be fully operational at this point. For further controller enhancement or operation detail, please consult the Advanced Programming section. 2100-566D...