Requires optional Bard 8403-061 Outdoor Air
Temperature Sensor.
NONE = No auxiliary strip heat; controller will
not energize W2. If NONE is chosen, press
LEFT button five (5) times to return to home
screen.
9. Press DOWN button to highlight DELAY (MINS).
10. Press ENTER button to highlight default DELAY
minutes.
11. Press UP or DOWN button to select amount
of minutes desired to delay the electric heat
before activation: 10-120 minutes, 10 minute
increments. Press ENTER button to save choice.
12. Press LEFT button to return to ADDITIONAL
SETUP.
If COMP LOCKOUT was chosen during the heat
strip configuration process, an optional outdoor air
temperature sensor will have to be installed/configured
to specifically set the temperature at which the
compressor will no longer be allowed to operate. To
install Bard 8403-061 Outdoor Air Temperature Sensor,
attach the leads to terminals "OAT" and "GND". To set
the compressor outdoor air temperature from the home
screen:
1. Press RIGHT button to access Main Menu screen.
2. Press DOWN button to scroll to ADVANCED. Press
ENTER button.
3. In the ADVANCED menu screen, press UP or
DOWN button to scroll to LIMITS. Press ENTER
button.
4. Press DOWN button to scroll to COMP OAT HTG
LOW. Press ENTER button.
5. Press UP or DOWN button to select outdoor air
temperature for compressor lockout. Press ENTER
to save choice.
6. Press LEFT button to return to ADVANCED menu.
Damper, Fan and Humidity Setup
1. In the ADVANCED menu screen, press ENTER
button to enter the APPLICATION menu.
2. Controller will ask for Admin Level Password.
Enter BARD or 1914. Press ENTER button.
3. Press DOWN button to scroll to ADDITIONAL
SETUP. Press ENTER button.
4. Press DOWN button to scroll to DAMPER. Press
ENTER button.
5. Press UP or DOWN button to choose from the
available economizer options:
NONE = No economizer, or standard vent
package (ERV/CRV/MFAD)
EN/DIS = Economizer in system
6. Press ENTER button to select/save appropriate
economizer option.
7. Press LEFT button to go back to ADDITIONAL
SETUP.
8. The indoor blower can be set for ON or AUTO
in either occupied or unoccupied conditions. To
access or change blower settings, press DOWN
button to scroll to FAN. Press ENTER button to
enter FAN SETUP.
9. Press DOWN button to scroll through selections;
adjust as necessary.
Speeds: Constant speed (nonadjustable)
Off Delay: "0" = System fan will run for
specified time after call ends; 0-600 seconds
in 30-second increments.
Unocc: "ON" = System fan will run
continuously during all operational modes;
"AUTO" = System fan will operate during call
for cooling or heating, but will cycle off when
no compressor or no heating is needed (factory
default).
Occ: "ON" = System fan will run continuously
during all operational modes (factory default);
"AUTO" = System fan will operate during call
for cooling or heating, but will cycle off when
no compressor or no heating is needed.
10. Press ENTER button to save changes to FAN mode
selections.
11. Press LEFT button to go back to ADDITIONAL
SETUP.
12. Press DOWN button to scroll to HUMIDITY. Press
ENTER button to enter HUMIDITY SETUP.
13. Press ENTER button again to choose
DEHUMIDIFICATION.
14. Press ENTER button again to highlight current
dehum choice (default is DISABLE).
15. Press UP or DOWN button to toggle ENABLE/
DISABLE. Press ENTER button to select/save
choice.
16. Press DOWN button to scroll through additional
DEHUMIDIFICATION screen choices:
ALLOW HTG DEHUM = Allows
dehumidification in heating as well as cooling:
YES/NO.
DEHUM SETPT = Relative Humidity
(RH) setpoint: 50% RH to 75% RH, 1%
increments.
Manual
2100-566F
Page
7 of 24