5.2.2

Properties of the base area

Properties of the base area
To ensure the stability of the charging station, the base area must meet the following
requirements:
• Level
• Dry
• Sufficiently solid and capable of bearing the load (e.g. concrete area in quality class
C30/37)
5.2.3

Minimum clearances

To operate, maintain and ensure ventilation of the charging station, maintain the following
minimum distances (in mm):
Required distance to raise and lower the charging station during installation.
Distance between charging stations.
At 100 ... 600 mm distance, you must move the charging station for maintenance.
At a distance of 600 mm or more, you can service the charging station without restriction.
Required distance at the front of the charging station
Required distance to open the control cabinet door by more than 90°. Less distance is permitted, but the opening
angle is smaller.
Figure 5-4  Minimum clearances
SICHARGE UC 150
Operating Instructions, 02/2023, A5E50068475-AB
Preparing for use
5.2 Location planning
51