Fluke CableAnalyzer DTX-1500 Technical Reference Handbook page 104

Hide thumbs Also See for CableAnalyzer DTX-1500:
Table of Contents

Advertisement

DTX-1500 CableAnalyzer
Technical Reference Handbook
To set the reference, do the following:
Turn on the tester and let it sit for 1 minute before
setting the reference. Set the reference only after
the testers have reached an ambient temperature
between 10
C and 40
1
Attach coaxial adapters to the main and remote
testers, screw in the F-connector to BNC adapters; then
make the connections shown in Figure 5-1.
2
Turn the rotary switch to SPECIAL FUNCTIONS.
3
Highlight Set Reference; then press
4
Press
.
5-2
Note
C (50
F and 104
F).
.
DTX-CHA003
DTX-CHA003
DTX-CHA003
COAX ADAPTER
COAX ADAPTER
COAX ADAPTER
PASS
TEST
FAIL
TALK
TONE
LOW BATTERY
F1
F2
F3
EXIT
TEST
ENTER
SAVE
AUTO
TEST
SINGLE
TEST
SETUP
SPECIAL
MONITOR
FUNCTIONS
TEST
TALK
TALK
Figure 5-1. Coaxial Reference Connections
X140.EPS