5. Unit installation
A protection wall should be constructed with a solid material that can block the sea breeze and the height and
width of the wall should be 1.5 times larger than the size of the outdoor unit. (Please secure more than 700 mm of
space between the protection wall and the outdoor unit for air circulation.)
2 Consider that the salt particles clinging to the external panels should be sufficiently washed off.
– When a product is installed at the seashore, periodically clean it with fresh water to remove attached salt deposits.
3 Make sure that the base of the unit is installed water level and therefore has optimum drainage. Because trapped
water at the bottom of the outdoor unit significantly promotes corrosion.
– Prevent blockage of the drain hole by foreign substance, by cleaning adequately.
– Make sure to clean the base plate adequately and regularly as dirt, sand and other substances stay moist and
promote corrosion.
4 If the product installed within 500 m of a seashore, special anti-corrosion treatment is required.
※ Please contact your local Samsung representative for further details.
5 When product is installed at a seashore, periodically clean it with water to remove attached salinity.
6 If the (protective) coating, or galvanised steel of the product is damaged during the installation or maintenance, make
sure to repair it.
7 Check the condition of the product periodically.
– Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by
Samsung (Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the product condition.
Selecting a location in cold climates
NOTE
• When operating the unit in a low outdoor ambient temperature, be sure to follow the instructions
described below
In heavy snowfall areas it is very important to select an installation location where the snow will not affect the unit. If
lateral snowfall is possible, make sure that the heat exchanger coil is not affected by the snow (If necessary construct a
lateral canopy)
1 Construct a large canopy.
2 Construct a pedestal.
– Install the unit high enough off the ground to prevent it being buried under snow.
Installer reference guide / Mono tank integrated type
① Snow-proof hood
② Frame
Estimated snow fall
Ground
33