8. System configuration
6) #509* :Smart Grid control
※ SG : Smart Grid
Main Menu
Sub Menu
(FSV)
Function
Others
Smart Grid Control
FSV 50**
• Similar to Power Peak Control, but more detailed. It allows power companies to provide four operating modes via
two digital inputs. Not only during power surge, but also when there is an abundance of power in the grid, the power
company can force remotely to store more energy in the system, to prevent grid overload situations.
• FSV #5091 should be set "1": to use Smart Grid control. (#5091 = 0 disable , #5091 = 1 use)
1
2
3
Operation Mode
Mode 1
Mode 2
Mode 3
Mode 4
• Mode 1 : Forced Thermo off of all system
• Mode 2 : Normal operation
– Normal control is performed.
Installer reference guide / Mono tank integrated type
504* | Power Peak Control
5051 | Frequency Ratio Control
5061 | Heat/DHW Capa. Ratio
508* | PV Control
509* | Smart Grid Control
50** | Others
501* | Outing
502* | DHW Saving
503* | TDM Variable (TDM Product only)
504* | Power Peak Control
5051 | Frequency Ratio Control
5061 | Heat/DHW Capa. Ratio
508* | PV Control
509* | Smart Grid Control
Description
Application
Setting Temp. Shift Value (Heat)
Setting Temp. Shift Value (DHW)
DHW Mode
4
5
6
7
8
9
10
11
12
SG READY Signal 2
SG READY Signal 1
SG Ready Signal 1
(#1,2 Pin)
1 (Short)
0 (Open)
0 (Open)
1 (Short)
509* | Smart Grid Control
5091 | Application
5092 | Setting Temp. Shift Value(Heat)
5093 | Setting Temp. Shift Value(DHW)
5094 | DHW Mode
FSV
5091
5092
5093
5094
13
14
15
16
17
18
19
20
SG Ready Signal 2
(#3,4 Pin)
0 (Open)
0 (Open)
1 (Short)
1 (Short)
Step Unit Default
Min.
-
-
0 (No)
0
0.5
˚C
2
2
0.5
˚C
5
2
-
-
0
0
Product Operation
Forced Thermo off operation
Normal operation
1 Step-up operation
2 Step-up operation
Max.
1 (Yes)
5
5
1
152