5. Unit installation
• Install the outdoor unit on a flat, stable surface that can support its weight and does not generate any unnecessary
noise and vibration.
• Position the outdoor unit so that the air flows directly towards the open area.
• Place the outdoor unit where there are no plants and animals because they may cause malfunction of outdoor unit.
• Maintain sufficient clearance around the outdoor unit, especially from a radio, computer, stereo system.
• The outdoor unit shall be installed in an open space that is always ventilated.
• For installation inside a building (this applies either to indoor or outdoor units installed inside) a minimum room floor
area of space conditioned is mandatory according to IEC 60335-2-40:2018 (see the reference table into either the
indoor or outdoor unit installation manual).
Do not install the air to water Heat Pump in following locations:
• A location where there are any potential dangerous substances like: combustible gas, carbon fiber, mineral oil, arsenic
acid, flammable dust, thinner or gasoline, etc.
• A location where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet. The copper pipe
or connection pipe may corrode and refrigerant may leak.
• A location where the outdoor unit can easily overheat by solar radiation or if the ambient temperature exceeds 35°C
during cooling mode. A larger installation space is required or a protection against direct solar radiation.
• A location where strong winds may affect the unit. Please also consider enough clearance to avoid issues with the
exhaust air from the unit if directed at people.
• A location where air is trapped and may short circuit over the unit. Or where not enough service space is available.
• A too narrow location, as it can lead to problems and potential damage to the product. Also it can lead to the injuries
during installation or service work.
• A location where not enough ventilation space exists, especially when installing multiple outdoor units. Obstacles may
disturb the airflow over the unit and can potentially cause short circuiting between exhaust air and inlet air and may
lead to malfunction.
When installing 1 outdoor unit
※ AE***BXYD*G/EU, AE***RXYD*G/EU
Wall on suction-side
Installer reference guide / Mono tank integrated type
300 or more
1,500 or more
When the air outlet is towards the wall
(Unit : mm)
30