D7212GV2 | Operation and Installation Guide | Specifications

Specifications

Table 23:

Specifications

Voltage Input
Primary:
(Power
Secondary:
Supply)
Current
Control Panel: Idle 200mA
Requirements
Refer to the Current Rating Chart for Standby Battery Calculations section in the D9412GV2/D7412GV2 Approved
Applications Compliance Guide (P/N: F01U003639) for the current draw requirements of other system components.
Power
All external connections are power-limited except battery terminals.
Outputs*
Continuous
Power Outputs
Alarm Power
Output
Switched Aux
Power
Fire and
Fire/Burglary
Systems
Minimum
10.2 VDC
Operating
Voltage
SDI Bus
SDI Bus A (+):
SDI Bus B (-):
Telephone
Connection:
Connections
Two telco lines:
Battery
Discharge
Discharge/
Cycle
Recharge
Schedule
Recharge
Cycle
Environmental
Temperature:
Relative
Humidity:
Arming
D720 Command Center, D1255 Command Center, D1256 Fire Command Center; D1257 Fire Alarm Annunciator;
Stations
D1260 Alpha V Command Center; Keyswitch
Point
On-board
Thresholds
Points 1 to 8
Compatible
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure, BATB-40 Battery Box
Enclosures
58
Terminals 1 and 2
16.5 VAC 40 VA class 2 plug-in transformer (D1640)
Terminals 4 and 5
Sealed lead-acid rechargeable battery (12 VDC, 7 Ah or 12 VDC, 17.2 or 18
Ah). The control panel supports up to two 12 VDC, 7 Ah batteries using the
D122 Dual Battery Harness or two D1218 (12 VDC, 17.2 or 18 Ah) batteries
using a D122.
Alarm 500 mA
Terminals 3, 24,
1.4 A maximum at 10.2 VDC to 13.9 VDC (continuous supply) total for all
and 32
devices and outputs supplied at Terminals 3, 24, and 32 and at the accessory
and programming connectors.
Terminals 6 and 7
2.0 A maximum at 10.2 VDC to 13.9 VDC output. Output can be steady or
one of three pulsed patterns depending on programming. Refer to Relays in
the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636).
Terminal 8
1.4 A maximum at 10.2 VDC to 13.9 VDC output. Continuous output is
interrupted by Sensor Reset or alarm verification depending on programming.
Refer to Relays in the D9412GV2/D7412GV2 Program Entry Guide (P/N:
F01U003636).
To comply with UL 985 and 864 listing standards for fire alarm systems (effective March 1, 1989),
the total combined continuous and alarm current draw for the system during alarm conditions must
be limited to 1.4 A provided by the primary power supply (rectified AC). If current draw for the
system exceeds 1.4 A, remove connected devices until the current draw falls below 1.4 A. Then,
connect the removed devices to a D8132 Battery Charger Module or to an external power supply
(refer to Figure 19 on page 46).
9 VDC 4572 m (15000 ft) maximum
9 VDC 4572 m (15000 ft) maximum
RJ31X or RJ38X jack can connect the control panels.
Bosch Security Systems D928 Dual Phone Line Module required for two phone line service.
Supervision supplied by the control panel.
13.9 VDC
Charging float level.
13.8 VDC
Charging status LED on.
12.1 VDC
Low Battery and AC Fail Reports if programmed. Low Battery LED on.
10.2 VDC
Minimum operational voltage
10.0 VDC
Battery load shed (processing functions continue if AC is present).
AC ON
Load shed relay resets, battery charging begins, Battery Trouble and AC
Restoral Reports sent.
13.7 VDC
Battery Restoral Report sent, Low Battery LED off.
13.9 VDC
Charging status LED off, battery float charged.
0°C to +50°C (+32°F to +122°F)
Maximum 95% non-condensing
Open
Greater than 3.7 VDC, but less than 5.0 VDC.
Normal
Greater than 2.0 VDC, but less than 3.0 VDC.
Short
Greater than 0.0 VDC, but less than 1.3 VDC.
Bosch Security Systems, Inc. | 5/05 | F01U003805B