A shorted battery condition is created either by a
shorted cell inside the battery or by a short on
Terminals 4 and 5. A shorted battery might cause the
control panel to operate in an unsafe way. This
condition generates WATCHDOG RESET reports.
5.2.6

Battery Discharge and Recharge Schedule

Table 7:
Battery Discharge and Recharge

Schedule

Discharge Cycle
AC Off:
AC Fail Report when AC fails, if
control panel is programmed to report
AC failure at occurrence.
13.9 VDC:
Charging float level.
13.8 VDC:
Charging status LED on.
12.0 VDC:
Low Battery and AC Fail Reports if
programmed. Low battery LED on.
< 10.0 VDC:
Battery load shed (processing
functions continue if AC is present).
Recharge Cycle
AC On:
Load shed relay reset; battery
charging begins; Battery Trouble and
AC Restoral Reports sent.
13.7 VDC:
Battery Restoral Reports sent. Low
battery LED off.
13.9 VDC:
Changing status LED off; battery float
charged.
22
Power Supply
Bosch Security Systems, Inc. | 5/05 | F01U003805B