6 Commissioning
6.2.6

Analog input (ADC)

Value x1 of ADC scaling
P0757 =...
Value y1 of ADC scaling
P0758 =...
This parameter represents the value
of x1 as a % of P2000 (reference
frequency).
Value x2 of ADC scaling
P0759 =...
Value y2 of ADC scaling
P0760 =...
This parameter represents the value
of x2 as a % of P2000 (reference
frequency).
Width of ADC deadband
P0761 =...
Defines width of deadband on analog
input.
ADC channel
6.2.7

Motor potentiometer (MOP)

Setpoint memory of the MOP
P1031 =...
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or
power down.
0
MOP setpoint will not be stored
1
MOP setpoint will be stored (P1040 is updated)
Inhibit negative MOP setpoints
P1032 =...
0
Neg. MOP setpoint is allowed
1
Neg. MOP setpoint inhibited
Setpoint of the MOP
P1040 =...
Determines setpoint for motor potentiometer control.
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121.
20
0 V
P0761 > 0
0 < P0758 < P0760
0.0 %
100 %
10 V
P0760
100.0 %
P0758
0 V
KL8
P0753
+10 V
KL9
A
KL10
D
1.7 V
1
0
3.9 V
Possible parameter settings for the selection of MOP:
Selection
P0719 = 0, P0700 = 2, P1000 = 1
DIN
or
P0719 = 1, P0700 = 2
P0719 = 0, P0700 = 1, P1000 = 1
or
BOP
P0719 = 1, P0700 = 1
or
P0719 = 11
P0719 = 0, P0700 = 5, P1000 = 1
or
)
USS *
P0719 = 1, P0700 = 5
or
P0719 = 51
*) SINAMICS G110 CPM110 USS only
||
0 > P0758 > P0760
%
4000 h
max
P0757
P0761
P0757 = P0761
min
r0754
P0761
P1000 = 2
ADC
ADC
dead
scaling
zone
r0752
P0704 = x
r0722
r0722.3
MOP up
MOP down
P0702 = 13
P0703 = 14
(DIN1)
(DIN2)
UP button
DOWN button
USS control word
USS control word
r2036 Bit13
r2036 Bit14
Operating Instructions (Compact)
Issue 11/04
V
x
10 V
100%
P0759
Setpoint
Function
0
1
5.00 Hz
SINAMICS G110