Commissioning; Quick Commissioning - Siemens SINAMICS G110 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G110:
Table of Contents

Advertisement

Issue 11/04
6

Commissioning

6.1

Quick commissioning

The quick commissioning function will adapt the inverter to the motor and will set
important technological parameters. The quick commissioning can be omitted if a
4-pole 1LA Siemens motor will be used, which matches the rating data of the
frequency inverter.
In order to have access to all motor parameters it is recommended to set the user
access level P0003=3 (see 5.2)
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
START
Commissioning parameter *
P0010 = 1
30
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
Europe/ North America
P0100 =...
(enters the default motor base frequency and power
settings hp/kW)
P0100 = 1
P0100 = 0, 2
NOTE
For P0100 = 0 or 1, the setting of the DIP switch
must be in line with the value of P0100 (refer to the
parameter list).
NOTICE
Motor parameters must be accurately
configured for motor overload protection
to operate correctly above 5 Hz.
P0304 =... P0304 =... Rated motor voltage
(Nominal motor voltage [V] from rating
plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to ensure
that it matches with the circuit
connection configured at the motor
terminal board
P0305 =... P0305 =... Rated motor current
(Nominal motor current [A] from rating plate)
P0307 =... P0307 =... Rated motor power
(Nominal motor power [kW/hp] from rating plate)
If P0100 = 0 or 2, value will be in kW. If P0100 = 1, value will be in in hp.
SINAMICS G110
Operating Instructions (Compact)
0
Ready
1
Quick commissioning
Factory setting
0
Europe [kW], frequency default 50 Hz
1
North America [hp], frequency default 60 Hz
2
North America [kW], frequency default 60 Hz
0
230 V
P0304
P0310
P0305
P0307
P0308 P0311
6 Commissioning
Factory setting
0
FU-spec.
FU-spec.
15