Commissioning The Application; Serial Interface (Uss) - Siemens SINAMICS G110 Operating Instructions Manual

Hide thumbs Also See for SINAMICS G110:
Table of Contents

Advertisement

Issue 11/04
Control mode
P1300 =...
(enters the required control mode)
End of quick commissioning
P3900 = 1
(means: the start of the motor calculation)
NOTE
For P3900 = 1,2,3
calculated (refer to the parameter list P0340).
P3900=3 is useful in case of motor change
End of quick commissioning/ drive setting
END
If additional functions must be implemented at the drive inverter, use the following
Section "Commissioning the application" . We recommend this procedure for
drives with a high dynamic response.
6.2

Commissioning the application

An application is commissioned to adapt/optimize the frequency inverter - motor
combination to the particular application. The frequency inverter offers numerous
functions - but not all of these are required for the particular application. These
functions can be ignored when commissioning the application. A large portion of
the possible functions are described here; refer to the parameter list for additional
functions.
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
START
User access level *
P0003 = 3
1
Standard (Allows access into most frequently used parameters)
2
Extended (Allows extended access e.g. to inverter I/O functions)
3
Expert (for expert use only)
6.2.1

Serial interface (USS)

USS baud rate
P2010 =...
Sets baud rate for USS communication.
USS address
P2011 =...
Sets unique address for inverter.
USS PZD length
P2012 =...
Defines the number of 16-bit words in PZD part of USS telegram.
USS PKW length
P2013 =...
Defines the number of 16-bit words in PKW part of USS telegram.
SINAMICS G110
Operating Instructions (Compact)
0
V/f with linear characteristic
2
V/f with quadratic characteristic
3
V/f with programmable characteristic
0
No quick commissioning (no motor calculations)
1
End quick commissioning, with factory reset of all other settings
2
End quick commissioning, with factory reset of I/O settings
3
End quick commissioning, without reset of all other settings
P0340 is internally set to 1 and the appropriate data
6 Commissioning
0
0
Factory setting
1
6
Possible
Settings:
3
1200 baud
0
4
2400 baud
5
4800 baud
6
9600 baud
2
7
19200 baud
8
38400 baud
9
57600 baud
127
17