5.3

Diagnostics alarms

A diagnostics alarm is output for each diagnostics event and the DIAG LED on the
module flashes. The diagnostics alarms can, for example, be read from the diagnostics
buffer of the CPU. You can evaluate the error codes with the user program.
Table 5- 4
Diagnostics alarms, their meaning and how to deal with them
Diagnostics alarm
Channel temporarily
unavailable
Short-circuit
Wire break
Parameter assignment
error
No load voltage
Digital output module DQ 8x24VDC/0.5A ST (6ES7132-6BF00-0BA0)
Manual, 07/2014, A5E03574575-AC
Error code
Meaning
1F
Firmware update is currently in progress
H
or has been canceled.
The module does not output any process
or substitute values in this state.
1
Short-circuit of actuator supply to
H
ground
Short-circuit of actuator supply to L+
6
Actuator circuit impedance too high.
H
Wire break between the module and
actuator
Channel not connected (open)
10
The module cannot evaluate
H
parameters for the channel.
Incorrect parameter assignment.
11
No or insufficient supply voltage L+
H
Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Remedy
Wait for firmware update
Restart the firmware update
Correct the process wiring
Use a different actuator type or wire
differently, e.g. use cables with a larger
cross-section
Connect the cable
Disable diagnostics
Connect a resistor to the actuator
contacts in the load resistance range
Correct the parameter assignment
Check supply voltage L+
on the BaseUnit
Check BaseUnit type
19