Operating Limits; Abbreviations And Definitions; Reference Calculations - York YAFS012 Manual

Submittal set, affinity & affinity advanced geothermal heat pumps, single and dual capacity, 1/2 thru 1.5/6 nominal tons
Hide thumbs Also See for YAFS012:
Table of Contents

Advertisement

Contractor:
Engineer:
Project Name:

Operating Limits

Operating Limits
Air Limits
Min. Ambient Air
Rated Ambient Air
Max. Ambient Air
Min. Entering Air
Rated Entering Air db/wb
80.6/66.2
Max. Entering Air db/wb
110/83
Water Limits
Min. Entering Water
Normal Entering Water
50-110
Max. Entering Water
Defi nitions

Abbreviations and Definitions

cfm
= airflow, cubic feet/minute
EWT = entering water temperature, Fahrenheit
gpm
= water flow in gallons/minute
WPD = water pressure drop, psi and feet of water
EAT
= entering air temperature, Fahrenheit (dry bulb/wet bulb)
HC
= air heating capacity, MBtu/h
TC
= total cooling capacity, MBtu/h
SC
= sensible cooling capacity, MBtu/h
kW
= total power unit input, kilowatts
HR
= total heat of rejection, MBtu/h
HE
= total heat of extraction, MBtu/h

Reference Calculations

Heating Calculations:
HE
LWT = EWT -
gpm x 500
HC
LAT = EAT +
cfm x 1.08
TH = HC + HW
Notes to Performance Data Tables
The following notes apply to all performance data tables:
• Performance ratings are based on 80°F DB/67°F WB EAT for cooling and 70°F DB EAT for heating.
• Three flow rates are shown for each unit. The lowest flow rate shown is used for geothermal open loop/well water systems with a minimum
of 50°F EWT. The middle flow rate shown is the minimum geothermal closed loop flow rate. The highest flow rate shown is optimum for
geothermal closed loop systems and the suggested flow rate for boiler/tower applications.
• The hot water generator numbers are based on a flow rate of 0.4 gpm/ton of rated capacity with an EWT of 90°F.
• Entering water temperatures below 40°F assumes 15% antifreeze solution.
• For non-standard EAT conditions, apply the appropriate Correction Factor tables.
• Interpolation between EWT, gpm, and cfm data is permissible, extrapolation is not.
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
SD2500AK6
11/22
P.O.:
Unit Tag:
Cooling
Heating
(°F)
(°C)
(°F)
45
7.2
45
80
26.7
70
100
37.8
85
50
10.0
40
27/19
68
43/28.3
80
30
-1.1
20
10-43.3
30-70
120
48.9
90
Cooling Calculations:
HR
LWT = EWT +
gpm x 500
LAT (DB) = EAT (DB) -
cfm x 1.08
LC = TC - SC
SC
S/T =
TC
(°C)
7.2
21.1
29.4
4.4
20.0
NOTE: Minimum/maximum limits are only for start-up conditions, and are meant
for bringing the space up to occupancy temperature. Units are not designed to
26.7
operate at the minimum/maximum conditions on a regular basis. The operating
limits are dependent upon three primary factors: 1) water temperature, 2) return
-6.7
air temperature, and 3) ambient temperature. When any of the factors are at the
-1.1
minimum or maximum levels, the other two factors must be at the normal level for
32.2
proper and reliable unit operation.
HWC = hot water generator capacity, MBtu/h
EER
= Energy Efficient Ratio
= Btu output/Watt input
COP = Coefficient of Performance
= Btu output/Btu input
LWT
= leaving water temperature, °F
LAT
= leaving air temperature, °F
TH
= total heating capacity, MBtu/h
LC
= latent cooling capacity, MBtu/h
S/T
= sensible to total cooling ratio
SC
19
Affinity & Affinity Advanced Series
1 - 6 Tons 60Hz
Page _____ of _____