York YAFS012 Manual page 51

Submittal set, affinity & affinity advanced geothermal heat pumps, single and dual capacity, 1/2 thru 1.5/6 nominal tons
Hide thumbs Also See for YAFS012:
Table of Contents

Advertisement

Contractor:
Engineer:
Project Name:
Wiring Schematics cont.
Aurora Base with PSC cont.
With optional EA Series 10kW Auxiliary Electric Heat Shown
1 - Use copper o r aluminum conductors.
2 – When Auxil iary Heat is installe d the BLK/WHT
wire from CC-L1 to PB2-2 and the GRY/WHT wire
from CC-L2 to PB2-1 must be removed (located in
the heat pump control box).
3 – Jumpers wi re s are Factory Installed, and are
Required for auxi liary heat operation.
4 – Low vol tage wiring CLASS 2.
Bro wn
To PB2
Orange
Blue
Violet
Green
1
2
3
4
5
P11
Connects to vari able
speed ECM motor only
Legend
Factory Low voltage wi ri ng
Light emi tting diode - Green
G
Factory Line vol tage wiring
Field low voltage wiring
Fi eld l ine voltage wi ring
FB
Fused Backup
Optional block
DC Voltage PCB traces
Internal junction
K*
Electric Heat Relay
Qui ck connect terminal
1 2 3
TS
Thermal Limi t Switch
P
Polarized connector
L1
Field wire lug
PB -
Power block
Ground
HE -
Heater element
N.O., N.C.
Bre aker
Communicating Thermostat
T o Fo ss il F u el
R f rom Foss il
Furnac e W input
Dual Fuel Wiring Diagr am
Fue l Furnac e
Using Field Installed Relay
Note 8: Fiel d i ns ta lled SPST dua l f ue l rel ay
(Re quired f or dual f uel i ns ta llat ion)
EH1
ABC
24 VDC
Board
C
Aurora LED Flash Codes
Slow Flash
1 second on and 1 second off
Fast Flash
100 milliseconds on and 100 milliseconds off
Flash Code
100 milliseconds on and 400 milliseconds off with a 2 second pause before repe ating
Random Start Delay (Alternating Colors)
Configuration LED (LED2, Yellow)
Status LED (LED1, Green)
Fast Flash
No Software Overi de
Configuration LED (LED2, Yellow)
Fast Fl ash
DIP Switch Overide
Faul t LED (LED3, Red)
Fast Fl ash
Fault LED (LED1, Red)
Sta tus LED (LED3, Green)
Normal Mode
OFF
Normal Mode
Input Fault Lockout
Fl ash Code 1
Control is Non-Functional
High Pressure Lockout
Fl ash Code 2
Test Mode
Low Pressure Locko ut
Fl ash Code 3
Lockout Active
Future Use
Fl ash Code 4
Dehumidification Mo de
Freeze De tecti on – FP1
Fl ash Code 5
Future Use
Reserved
Fl ash Code 6
Future Use
Condensate Overflow Lockout
Fl ash Code 7
Load Shed
Over/Under Voltage Shutdown
Fl ash Code 8
ESD
Future Use
Fl ash Code 9
Future Use
Future Use
Fl ash Code 10
FP1 Senso r Error
Fl ash Code 11
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
SD2500AK6
11/22
P.O.:
Unit Tag:
208-230/60/1
P9
1
G
L1
L2
2
Green
3
5
Bro wn
4
Orange
TB
Black
K1
Gray
Gray
FB1
G
NO
K2
Black
FB2
G
NO
Gray
K3
Gray
NO
G
Black
K4
NO
G
EA Seri es PCB
P2
P1
C
1
2
3
4
C
1
2
3
4
NOTE 3
CO
C EH1 C
EH2
P3
Condensate
P3 on Aurora ABC Board
Legend
Factory Low voltage wi ri ng
Factory Line vol tage wiring
Fi eld l ow voltage wiring
Fi eld l ine voltage wi ring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
Wire nut
Field wire lug
L1
Ground
Relay Con tacts-
2
N.O., N.C.
P
OFF
Fuse
Slow Flash
Bre aker
ON
CC -
Compressor Contactor
OFF
CO -
Condensate overflow sensor
K5 -
DHW pump relay
Slow Flash
Loop pump relay
K6 -
Fast Fl ash
CR3 -
PSC Fan Speed Relay
Fl ash Code 2
PSC Fan Power Relay
CR4 -
Flash Code 3
CS -
Compressor Solenoid
Fl ash Code 4
F1 and F2 -
Fuses
Fl ash Code 5
HE -
Heater element
Fl ash Code 6
HP -
High pressure switch
Fl ash Code 7
ER1 to ER4 -
Aux heat stage relays
LP -
Low pressure switch
Black
Gray
HE1
TS1
HE2
TS2
Black
Thermistor
T
Light emi tting diode - Green
G
Relay coil
Capacitor w/ bleed resi stor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
3
1
Polarized connector
Current Transducer (CT)
PB1, PB2 -
Power blocks
PS -
Power strip
RV -
Reversi ng Valve coil
SW1 -
DIP package 5 position AXB
SW1 -
TEST MODE ABC Board
SW2 -
DIP package 8 position ABC Board
TS -
Thermal limit swi tch
HWL -
Hot water limit sensor
SC -
Start Contactor
SR -
Start Relay
WCL -
Water Coil Limit Sensor
51
Affinity & Affinity Advanced Series
1 - 6 Tons 60Hz
Page _____ of _____

Advertisement

Table of Contents
loading

Table of Contents