AHRI/ISO 13256-1 Performance Ratings
Variable Speed ECM or 5-Speed ECM Motor
AHRI/ASHRAE/ISO 13256-1
English (IP) Units
Flow Rate
Capacity
Model
Modulation
gpm
026
Full
8
026
Part
7
038
Full
9
038
Part
8
049
Full
12
049
Part
11
064
Full
16
064
Part
14
072
Full
18
072
Part
16
5
018
Single
022
Single
8
030
Single
8
036
Single
9
042
Single
11
048
Single
12
060
Single
15
070
Single
18
NOTE: 018 not available with 5-Speed ECM motor
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All ratings based upon 208V operation
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
SD2500AK6
11/22
P.O.:
Unit Tag:
Water Loop Heat Pump
Cooling
EWT 86° F
Capacity
EER
Capacity
cfm
Btuh
Btuh/W
950
24,900
16.8
30,100
750
18,900
18.6
22,000
1300
36,500
17.0
43,300
1150
26,500
19.0
31,300
1600
49,100
17.2
59,000
1400
36,300
19.1
41,700
1800
62,300
16.4
73,900
1500
45,800
18.1
53,200
2000
70,100
15.6
88,000
1500
54,200
17.0
66,000
600
17,400
15.7
23,000
800
18,100
15.6
23,700
1000
27,000
18.9
32,900
1200
32,300
18.8
36,500
1300
39,000
18.6
45,600
1500
44,100
16.3
55,600
1800
61,100
16.4
74,100
2000
66,200
15.3
85,000
Ground Water Heat Pump
Heating
Cooling
EWT 68° F
EWT 59° F
Capacity
EER
COP
Btuh
Btuh
Btuh/W
5.5
27,700
24.0
6.1
22,200
29.7
5.5
40,000
24.4
6.4
29,900
32.1
5.5
54,100
24.5
6.1
41,600
33.0
5.2
69,000
23.9
5.9
53,000
30.7
4.8
79,000
22.0
5.1
61,500
27.6
5.3
20,600
26.0
6.0
21,900
27.5
5.6
31,200
29.5
5.7
36,800
28.8
5.8
43,900
28.1
5.4
50,300
25.9
5.5
66,900
24.3
5.0
75,000
22.9
3
Affinity & Affinity Advanced Series
1 - 6 Tons 60Hz
Ground Loop Heat Pump
Cooling Brine
Heating
Full Load 77° F
EWT 50° F
Part Load 68° F
Capacity
Capacity
COP
EER
Btuh
Btuh
23,900
4.8
26,400
19.6
17,500
4.9
21,000
26.0
35,000
4.9
38,200
19.7
24,900
5.1
29,500
28.0
47,200
4.6
50,800
19.3
33,600
4.7
39,800
27.4
60,400
4.6
65,500
19.3
43,500
4.8
50,500
26.5
71,000
4.3
73,800
18.2
52,700
4.3
59,400
24.9
18,700
4.6
18,500
18.3
19,500
5.0
19,200
18.7
26,000
4.8
28,100
22.0
29,200
4.9
33,700
22.0
36,100
4.9
40,700
21.7
44,700
4.7
45,900
18.8
59,200
4.7
62,200
18.4
68,000
4.4
69,100
17.6
Page _____ of _____
Heating Brine
Full Load 32°F
Part Load 41°F
Heating
COP
Capacity
19,500
4.0
16,400
4.5
28,500
4.2
22,900
4.8
38,200
4.0
31,000
4.4
47,300
3.8
35,700
4.3
55,400
3.7
47,400
3.9
14,500
3.8
15,000
4.0
20,500
3.9
24,400
4.2
28,900
4.0
36,400
4.0
47,900
4.0
54,000
3.7