Operating Limits; Operation Logic Data Table - York AFFINITY YAFT026 Installation Manual

Geothermal heat pumps single and dual capacity
Hide thumbs Also See for AFFINITY YAFT026:
Table of Contents

Advertisement

Operating Limits

Operating Limits
Air Limits
Min. Ambient Air
Rated Ambient Air
Max. Ambient Air
Min. Entering Air
Rated Entering Air db/wb
80.6/66.2
Max. Entering Air db/wb
Water Limits
Min. Entering Water
Normal Entering Water
Max. Entering Water

Operation Logic Data Table

Operation Logic Table
STG1
Compressor
Reversing Valve
Aux Heat
Acc Relay
Fan Relay (PSC)
Loop Pump
Hot Water
Med Low
5-Speed ECM Speed
ECM Speed
Med
T-Stat Signal
AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Cooling
Heating
(°F)
(°C)
(°F)
45
7.2
45
80
26.7
70
100
37.8
85
50
10.0
40
27/19
68
110/83
43/28.3
80
30
-1.1
20
50-110
10-43.3
30-70
120
48.9
90
Heating
STG2
STG3
On
On
On
Off
Off
Off
Off
Off
Staged
On
On
On
On
On
On
On
On
On
On
On
Off
Med High
High
High
Aux
Y1
Y1,Y2
Y1,Y2,W
(°C)
7.2
21.1
29.4
4.4
NOTE: Minimum/maximum limits are only for start-up conditions, and
20.0
are meant for bringing the space up to occupancy temperature. Units
26.7
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependent upon three primary
-6.7
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
-1.1
levels, the other two factors must be at the normal level for proper and
32.2
reliable unit operation.
EMERG
Fan Only
Off
Off
Off
Off
Staged
Off
Off
Off
On
On
Off
Off
Off
Off
High
Low
Aux
Low
W
G
65
Cooling
STG1
STG2
Reheat
On
On
On
On
On
On
Off
Off
Off
On
On
On
On
On
On
On
On
On
On
On
NA
Med Low
Med High
High
Med
High
High
Y1,O
Y1,Y2,O
DH
Fan Only
Off
On
Off
Off
On
Off
Off
Low
Low
G
5/11/12