Air flow values are with dry coil and standard filter
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by
0.16 in. wg.
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
SD2500AK6
11/22
P.O.:
Unit Tag:
0
0.05
0.10
0.15
0.20
480
450
440
420
410
440
410
400
380
370
395
370
360
340
330
325
310
300
280
270
Airflow (cfm) at External Static Pressure (in. wg)