Model 049 - Full Load Dual Capacity with Variable Speed ECM or 5-Speed ECM (1550 cfm)
Flow
EWT
WPD
Rate
Airflow
°F
GPM
CFM
PSI
FT/HD
6.0
1.3
3.0
9.0
2.5
5.7
20
1350
12.0
4.0
9.2
1550
6.0
1.2
2.9
1350
9.0
2.4
5.5
30
1550
1350
12.0
3.9
8.9
1550
6.0
1.2
2.8
1350
9.0
2.3
5.3
40
1550
1350
12.0
3.7
8.7
1550
1350
6.0
1.2
2.7
1550
1350
50
9.0
2.2
5.2
1550
1350
12.0
3.6
8.4
1550
1350
6.0
1.1
2.6
1550
1350
60
9.0
2.2
5.0
1550
1350
12.0
3.5
8.1
1550
1350
6.0
1.1
2.5
1550
1350
70
9.0
2.1
4.9
1550
1350
12.0
3.4
7.9
1550
1350
6.0
1.1
2.5
1550
1350
80
9.0
2.0
4.7
1550
1350
12.0
3.3
7.6
1550
1350
6.0
1.0
2.4
1550
1350
90
9.0
2.0
4.5
1550
1350
12.0
3.2
7.3
1550
6.0
1.0
2.3
9.0
1.9
4.4
100
12.0
3.1
7.1
6.0
1.0
2.2
9.0
1.8
4.2
110
12.0
2.9
6.8
6.0
0.9
2.1
9.0
1.7
4.0
120
12.0
2.8
6.5
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.