York YAFS012 Manual page 43

Submittal set, affinity & affinity advanced geothermal heat pumps, single and dual capacity, 1/2 thru 1.5/6 nominal tons
Hide thumbs Also See for YAFS012:
Table of Contents

Advertisement

Contractor:
Engineer:
Project Name:
Wiring Schematics cont.
Aurora Advanced with ECM and IntelliStart cont.
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered
trademarks of Johnson Controls, Inc., and are used with permission.
SD2500AK6
11/22
P.O.:
Unit Tag:
P9
P9
1
1
2
2
3
3
5
5
4
4
Violet
Violet
Blue
Blue
P11
Green
Green
1
1
2
2
3
3
4
4
16 1 3 3
Connects to vari able
Connects to vari able
speed ECM motor only
speed ECM motor only
1 - Switch blue and red wires for 208V operation.
1 - Switch blue and red wires for 208V operation.
2 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
2 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
3 – When Auxiliary Heat is field installed the harness will then be connected to
3 – When Auxiliary Heat is field installed the harness will then be connected to
the auxiliary heat unit. The auxiliar y heat unit will then power the blower. Refer to
the auxiliary heat unit. The auxiliar y heat unit will then power the blower. Refer to
EAS/EAM/EAL Auxiliary Heat kit installation instructions.
EAS/EAM/EAL Auxiliary Heat kit installation instructions.
4 – Low voltage wiring CLASS 2.
4 – Low voltage wiring CLASS 2.
5 – Br own blower power wir e routed through Current Transducer two times.
5 – Br own blower power wir e routed through Current Transducer two times.
6 – Field Connected: Refer to Installation Manual and Auxiliary Heat Instructions for
6 – Field Connected: Refer to Installation Manual and Auxiliary Heat Instructions for
Cur rent Transducer installation.
Cur rent Transducer installation.
7 - Wires provided for Auxiliar y Heat low voltage contr ol. W ires are secured at blower.
7 - Wires provided for Auxiliar y Heat low voltage contr ol. W ires are secured at blower.
8 - Wiring harness supplied with valve.
8 - Wiring harness supplied with valve.
9 - On units with the NIDEC ECM motor the P13 harness connects to the
jumper harness on the motor.
on
Heat
d
43
Affinity & Affinity Advanced Series
With optional EA Series 20kW Auxiliary Electric Heat Shown
With optional EA Series 20kW Auxiliary Electric Heat Shown
60 AMP
60 AMP
60 AMP
60 AMP
BRK2
BRK2
BRK1
BRK1
L2
L2
L1
L1
L2
L2
L1
L1
G G
G
G
G G
Bro wn
Bro wn
Orange
Orange
Pink
Pink
Black
Black
Gray
Gray
Yellow
Yellow
K1
K1
Gray
Gray
G
G
COM
COM
NO
NO
K2
K2
5
5
P11
P11
Black
Black
COM
COM
G
G
NO
NO
K3
K3
Yellow
Yellow
COM
COM
NO
NO
G
G
K4
K4
Pink
Pink
COM
COM
G
G
NO
NO
EA Seri es
EA Seri es
PCB
PCB
C
C
1
1
2
2
3
3
4
4
P2
P2
C
C
1
1
2
2
3
3
4
4
NOTE 3
NOTE 3
CO
CO
CO
C EH1 C
C EH1 C
C EH1 C
EH2
EH2
EH2
P3
P3
P3
P3 on Aurora ABC Board
P3 on Aurora ABC Board
Notes
Notes
Notes
L1
L1 L1
CC -
CC -
CO -
CO -
K6
K6
K5
K5
CR3 -
CR3 -
CR4 -
CR4 -
CS -
CS -
F1 and F2 -
F1 and F2 -
HE -
HE -
HP -
HP -
ER1 to ER4 -
ER1 to ER4 -
LP -
LP -
1 - 6 Tons 60Hz
Legend
Legend
Legend
Factory Low voltage wi ri ng
Factory Low voltage wi ri ng
Factory Low voltage wi ri ng
Light emi tting diode - Green
Light emi tting diode - Green
Light emi tting diode - Green
G
G
G
Factory Line vol tage wiring
Factory Line vol tage wiring
Factory Line vol tage wiring
Fi eld l ow voltage wiring
Fi eld l ow voltage wiring
Fi eld l ow voltage wiring
FB
FB
FB
FB
Fused Backup
Fused Backup
Fused Backup
Fused Backup
Fi eld l ine voltage wi ring
Fi eld l ine voltage wi ring
Fi eld l ine voltage wi ring
Optional block
Optional block
Optional block
K*
K*
K*
K*
Electric Heat Rel ay
Electric Heat Rel ay
Electric Heat Rel ay
DC Voltage PCB traces
DC Voltage PCB traces
DC Voltage PCB traces
Internal juncti on
Internal juncti on
Internal juncti on
Qui ck connect terminal
Qui ck connect terminal
Qui ck connect terminal
1 2 3
1 2 3
1 2 3
P
P
P
Polarized connector
Polarized connector
Polarized connector
TS
TS
TS
Thermal Limi t Switch
Thermal Limi t Switch
Thermal Limi t Switch
PB -
PB -
PB -
Power block
Power block
Power block
L1
L1
L1
Fi eld wi re lug
Fi eld wi re lug
Fi eld wi re lug
HE -
HE -
HE -
Heater element
Heater element
Heater element
Ground
Ground
Ground
Bre aker
Bre aker
Bre aker
N.O., N.C.
N.O., N.C.
N.O., N.C.
K5
K5
Gray
Gray
FB1
FB1
HE1
HE1
HE1
TS1
TS1
TS1
TS1
COM
COM
NO
NO
Gray
Gray
K6
K6
Black
Black
COM
COM
NO
NO
HE2
HE2
HE2
FB2
FB2
TS2
TS2
TS2
TS2
Black
Black
Yellow
Yellow
K7
K7
FB3
FB3
HE3
HE3
HE3
TS3
TS3
TS3
TS3
COM
COM
NO
NO
Yellow
Yellow
Pink
Pink
K8
K8
FB4
FB4
HE4
HE4
HE4
COM
COM
NO
NO
TS4
TS4
TS4
TS4
Pink
Pink
P1
P1
Aux heat stagi ng
Aux heat stagi ng
1 - Use copper conductors.
1 - Use copper conductors.
1 - Use copper conductors.
2 - Use manufacturer's part number 19P592-01 (j umper
2 - Use manufacturer's part number 19P592-01 (j umper
2 - Use manufacturer's part number 19P592-01 (j umper
bar assembly) when singl e source power is required.
bar assembly) when singl e source power is required.
bar assembly) when singl e source power is required.
3 – Jumpers wi re s are Factory Installed, and are
3 – Jumpers wi re s are Factory Installed, and are
3 – Jumpers wi re s are Factory Installed, and are
required for a uxi liary heat operation.
required for a uxi liary heat operation.
required for a uxi liary heat operation.
4 – Low vol tage wiring CLASS 2.
4 – Low vol tage wiring CLASS 2.
4 – Low vol tage wiring CLASS 2.
Legend
Legend
Factory Low voltage wi ri ng
Factory Low voltage wi ri ng
Thermistor
Thermistor
T T
T
Factory Line vol tage wiring
Factory Line vol tage wiring
Fi eld l ow voltage wiring
Fi eld l ow voltage wiring
Light emi tting diode - Green
Light emi tting diode - Green
G G
G
Fi eld l ine voltage wi ring
Fi eld l ine voltage wi ring
Optional block
Optional block
Relay coil
Relay coil
DC Voltage PCB traces
DC Voltage PCB traces
Junction
Junction
Capacitor w/ bleed resi stor
Capacitor w/ bleed resi stor
Qui ck connect terminal
Qui ck connect terminal
Switch - Condensate overflow
Switch - Condensate overflow
Wire nut
Wire nut
Switch - High pressure
Switch - High pressure
Fi eld wi re lug
Fi eld wi re lug
Switch - Low pressure
Switch - Low pressure
Ground
Ground
Relay Con tacts-
Relay Con tacts-
2
2
2
3
3
3
1
1
1
Polarized connector
Polarized connector
N.O., N.C.
N.O., N.C.
P
P
P
Fuse
Fuse
Current Transducer (CT)
Current Transducer (CT)
Bre aker
Bre aker
Compressor Contactor
Compressor Contactor
PB1, PB2 -
PB1, PB2 -
Power blocks
Power blocks
PS -
PS -
Power strip
Power strip
Condensate overflow sensor
Condensate overflow sensor
RV -
RV -
Reversi ng Valve coil
Reversi ng Valve coil
DHW pump relay
DHW pump relay
Loop pump relay
Loop pump relay
SW1 -
SW1 -
DIP package 5 position AXB
DIP package 5 position AXB
PSC Fan Speed Relay
PSC Fan Speed Relay
SW1 -
SW1 -
TEST MODE ABC Board
TEST MODE ABC Board
PSC Fan Power Relay
PSC Fan Power Relay
SW2 -
SW2 -
DIP package 8 position ABC Board
DIP package 8 position ABC Board
Compressor Solenoi d
Compressor Solenoi d
TS -
TS -
Thermal limit swi tch
Thermal limit swi tch
Fuses
Fuses
HWL -
HWL -
Hot water limit sensor
Hot water limit sensor
Heater element
Heater element
SC -
SC -
Start Contactor
Start Contactor
High pressure switch
High pressure switch
SR -
SR -
Start Relay
Start Relay
Aux heat stage relays
Aux heat stage relays
WCL -
WCL -
Water Coil Limit Sensor
Water Coil Limit Sensor
Low pressure switch
Low pressure switch
Page _____ of _____