Model 072 - Part Load Dual Capacity with Variable Speed ECM or 5-Speed ECM (1700 cfm)
Flow
EWT
WPD
Rate
Airflow
°F
GPM
CFM
PSI
FT/HD
10.0
2.3
5.4
13.0
3.6
8.2
20
1400
16.0
5.0
11.6
1700
10.0
2.3
5.3
1400
13.0
3.5
8.0
30
1700
1400
16.0
4.9
11.3
1700
10.0
2.2
5.1
1400
13.0
3.4
7.8
40
1700
1400
16.0
4.7
11.0
1700
1400
10.0
2.1
4.9
1700
1400
50
13.0
3.3
7.5
1700
1400
16.0
4.6
10.6
1700
1400
10.0
2.1
4.8
1700
1400
60
13.0
3.2
7.3
1700
1400
16.0
4.4
10.3
1700
1400
10.0
2.0
4.6
1700
1400
70
13.0
3.0
7.0
1700
1400
16.0
4.3
9.9
1700
1400
10.0
1.9
4.5
1700
1400
80
13.0
2.9
6.8
1700
1400
16.0
4.2
9.6
1700
1400
10.0
1.9
4.3
1700
1400
90
13.0
2.8
6.6
1700
1400
16.0
4.0
9.3
1700
10.0
1.8
4.2
13.0
2.7
6.3
100
16.0
3.9
8.9
10.0
1.7
4.0
13.0
2.6
6.1
110
16.0
3.7
8.6
10.0
1.7
3.8
13.0
2.5
5.8
120
16.0
3.6
8.2
The manufacturer works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice. Purchaser's approval of this data set signifi es that the equipment is acceptable under the provisions
of the job specifi cation. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely the manufacturer's opinion or commendation of its products. York and Affi nity are registered