Installing the Cellular Router

Installation procedures will vary depending on the cellular signal strength at the BAS location.
Strong Cellular Signal Strength (max. bars or ≥ −75 dB)
When the cellular signal strength is strong at the BAS location, install the Digi cellular router inside the
Trane enclosure, using the Internal Mount Kit (Part# IX10-TRANEKIT-INTERNAL-DATA).
1. Prepare the enclosure for antenna mounting by opening a 3/4 in. knockout.
2. Attach the provided DIN rail clip to the Digi cellular router. (Trane technician to provide DIN rail, if
3. Mount the Digi cellular router inside the Trane Enclosure.
4. Attach provided coax cables directly onto the Digi cellular router.
5. Mount the provided antennas onto the outside of the enclosure, then attach the coax cables.
6. Connect the Digi cellular router to Ethernet Port 2 on the Tracer BAS controller using an Ethernet
7. Connect power to Digi cellular router:
Moderate or Poor Cellular Signal Strength (less than max. bars or ≥ −91
dB)
When the cellular signal strength is moderate or poor at the BAS location, install the Digi cellular router
in a remote location from the BAS using the Remote Mount Kit (Part# IX10-TRANEKIT-REMOTE-
DATA).
1. Mount the remote enclosure on a wall near the electrical receptacle.
2. Connect the Digi cellular router to Ethernet Port 2 on the Tracer BAS controller using an Ethernet
3. Connect power to the Digi cellular router remote enclosure.
Note: If obtaining a good signal at the required customer wall/receptacle location is still not possible,
BAS-SVX067H-EN
necessary).
cable.
Trane technician to provide bare red and black wire connection to the Digi cellular router
terminal block power connector.
Connect the PM014 power supply to the bare wire and terminal block power connector to the
Digi cellular router.
There are two IMC terminal connections on the PM014 power supply. Connect both wires
into either the left or the right IMC terminal connection. (See the following figure.)
Figure 1. PM014 power supply IMC terminal connections
Red wire
Black wire
cable.
Note: Maximum cable length is 300 ft.
consider purchasing a more powerful external antenna that can be mounted inside or outside of
the building by using the antenna cabling lengths available (75/50/7).
Black wire
Red wire