Download Print this page

Toshiba GR-200 Series Instruction Manual page 731

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Table 10.2-63 Detailed error information in IEC61850error
Error#
Function error found
0002
Failure occurred on going through the
0003
selection process with regard to the protocol
Failure occurred during initialization of
0004
protocol process
Failure for opening file
0005
0006
Failure of access
0007
No buffer space
No space left in the buffer provided for the
0008
SSP mapping
Failure of memory allocation in the memory
0009
dynamically
000A
Check sum errors
Failure of object search
000B
Failure of the defining of data type
000C
The second of that (i.e., "0004") is a reason (see Table 10.2-63), and it turns
out the 61850 initialization.
The top right and the middle left parts are the Data ID of the reason (i.e.,
"51200131" and "03011001"; the user can combine them into "512001
3103011001").
The others are used to show the name of the 61850 logical data. Figure
10.2-1 has "4747494F, 32245354, 7456616C" codes, so the user can convert
the codes to the "GGIO2$STtVal" message using Hexadecimal to ASCII
conversion method.
Reasons of errors
messages
- 712 -
Error#
Erroneous index being used in the data
000D
for the protocol stack designated
000E
Time out
000F
Going through the process
0010
Found invalid arguments
0011
Found the data type not being supported
Failure of the acquisition of the authority
0012
right
0013
Failure occurred on the setting process
0014
Failure of the event registration
0015
No event occurred
0016
Restarting
0017
Communication error
6F2T0200 (0.15)
Messages
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2