Dielectric voltage testing shall be carried out after reading the below notices carefully.
Cable connections
Figure-8 illustrates external connection around the power supply. During dielectric voltage testing,
short-wires attached around the power supply shall be carefully handled; follow the below
instructions (1) and (2).
(1) The short-wire between terminal screw No.17 and No.18
Remove the short-wire for undertaking the dielectric voltage test. If the short-wire is not
removed, the IED will be damaged.
After the test, reconnect the short-wire to the original positons.
(2) The short-wire between terminal screw No.17 and FG
Never remove the short-wire. If the short-wire is removed, the IED will be damaged.