Scheme logic of the restart inhibit function
(iii)
Figure 2.28-18 shows the scheme logic of the restart inhibit function constructed by the
thermal state of rotor function and the starts per hour function.
The signal "Mot-RSIH CBBLK" used to block CB closing is generated by the operating of the
thermal state of rotor function and the starts per hour function. In addition, the signal "Mot-
RSIH CBCLPERM" is made by inverting the signal "Mot-RSIH CBCLBLK", which is used to
permit CB closing.
The user must construct the CB closing circuit by using the programmable BOs or PLC logic
with the signal "Mot-RSIH CBBLK" or "Mot-RSIH CBCLBLK".
Thermal state of rotor
8000411C23
Mot-THSR
Mot-THSR-EN
On
MotSt-Irreg-Op
850000EBB7
Mot-THSR_BLOCK
Starts per hour
8000001B74
Mot-STPH
Reset the judgement
800000EBB9
Mot-STPH_RESET
Mot-STPH-EN
On
MotSt-Irreg-Op
860000EBB8
Mot-STPH_BLOCK
810000EBB1
Mot-EMR_START
Figure 2.28-18 Scheme logic of the restart inhibit function
8000001B73
Mot-THSR-ALARM
&
&
1
8100001B75
Mot-STPH-ALARM
&
&
1
1
- 342 -
8F00001B76
Mot-RSIH-ALARM
≥1
&
6F2T0200 (0.15)
8000001B77
Mot-RSIH-CBCLBLK
8100001B78
1
Mot-RSIH-CBCLPERM
GRE200 (1,2)