Toshiba GR-200 Series Instruction Manual page 1014

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

INF
144
145
Semantics
I
I, V
V0
Ve
Vs
P
Q
f
Note: The above coefficients are derived with the following equations:
(1) Currents in three-phase (I L1 , I L2 , I L3 ) and in symmetrical component (I1, I2, I0):
where,
For example, in In=1A , we can have coefficient 1706.666667.
(2) Earth fault current (I e ) and I e used for SEF (I se ) :
where,
For example, in In=1A , we can have coefficient 3413.333333.
(3) Voltages in three-phase (V L1 , V L2 , V L3 ), in symmetrical component (V1, V2, V0), in earth-
fault (Ve) , and in reference (Vs):
where,
For example, in Vn=110V , we can have coefficient 53.74606142.
146
147
148
Ia,Ib,Ic,
I1,I2,I0,Ie,Ise
I, V,
IN,
Va,Vb,Vc,V1,
P, Q
VEN
V2,V0,Ve,Vs,
P, Q, f
OK
OK
OK
OK
OK
OK
OK
OK
OK
Coefficient=
In:
Secondary current rating
Coefficient=
In:
Secondary current rating (or Ise rating current)
Coefficient=
Vn:
Secondary phase-phase voltage rating
Correspon
Corresponded
ded
Data ID in
Function
primary values
ID
(V2 secondary)
711081
0x711081
4302061056
(V0 secondary)
711081
0x711081
4302c31056
(V4 primary)
711081
0x711081
4302081056
(Vs primary)
711081
0x711081
43030b1098
(P)
711081
0x711081
43040c1098
(Q)
711081
0x711081
43060f105C
(f)
4096
In×2.4
4096
In×1.2
4096
Vn
×1.2
√ 3
- 995 -
6F2T0200 (0.15)
Coefficients
MEA
53.74606142
3413.333333
53.74606142
3413.333333
53.74606142
3413.333333
2.23942E-06
1706.666667
2.23942E-06
1706.666667
68.26666667
3413.333333
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2