Functional data (5/6)
Autoreclose (ARC)
Number of shots
Dead time for single-phase autoreclose
Dead time for three-phase autoreclose
Multi-shot dead line time
Reclaim time
Pulse width of reclosing signal output
Autoreclose reset time
Reset time for developing fault
Synchronism check (VCHK)
Synchronism check angle
UV element
OV element
Busbar or line dead check
Busbar or line live check
Synchronism check time
Voltage check time
Fault Locator (FL)
Line reactance and resistance setting
Line length
Correction factor of impedance between lines
Correction factor of impedance between in each
phase
Accuracy
1 – 5 shots
0.01 – 300.00s in 0.01s steps
0.01 – 300.00s in 0.01s steps
0.01 – 300.00s in 0.01s steps
0.0 – 600.0s in 0.1s steps
0.01 – 10.00s in 0.01s steps
0.01 – 310.00s in 0.01s steps
0.01 – 300.00s in 0.01s steps
0° – 75° in 1° steps
10 – 150V in 1V steps
10 – 150V in 1V steps
0 – 150V in 1V steps
0 – 150V in 1V steps
0.01 – 100.00s in 0.01s steps
0.01 – 100.00s in 0.01s steps
0.00 – 1000.00 in 0.01 steps
0.0 to 500.0km in 0.1km steps
50 to 150% in 1% steps
50 to 150% in 1% steps
±0.4km (up to 20km, without fault at near end)
±2.5% (up to 500km, without fault at near end)
- 1023 -
6F2T0200 (0.15)
GRE200 (1,2)