Download Print this page

Toshiba GR-200 Series Instruction Manual page 478

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Note: To identify the input and output signal-points of the other DPOS logics, see Table
††
4.1-14 for PLC#2, Table 4.1-15 for PLC#3, Table 4.1-17 and Table 4.1-19 for output
signals.
Note: The "Operate failed" signal is issued when the state-change is not detected until
‡‡
after reaching the time set by the [DPOS01-RST].
Operate condition
(vii)
In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.1-31 illustrates the logic to
examine
an
operate
"DPOS01_3PH_STATE". If the functionality of the original logic does not meet with user-
requirements, the following alternatives are available:
1. The user can replace the original logic with alternative logic.
2. The user can add another signal to the original logic.
Replacing the original logic
If the user wishes to replace the operate condition logic completely, it can be achieved using
connection point "User configurable condition":
1.
Connect the user-customized logic using "DPOS01IN_TMP_39", listed as PLC#2 in
Table 4.1-16.
2.
Set scheme switch [DPOS01-LGEXFFCT] to PLC.
Adding another operate condition signal
If the addition of another signal is required, the user can add the signal to the operate condition
logic using connection point "Additional condition"
1.
Add a user-preferred signal using DPOS01IN_TMP_38, listed as PLC#1 in Table
4.1-16.
2.
Set scheme switch [DPOS01-LGEXFFCT] to Fixedlogic.
condition;
the
operate
- 459 -
condition
is
determined
6F2T0200 (0.15)
by
signal
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2