Configuring With Step 7 And S7-Pct; Configuring With Step 7 And S7-Pct /Gsd Variant) - Siemens 3RS2 Manual

Monitoring and control devices temperature monitoring relay
Table of Contents

Advertisement

Digital devices with IO-Link
6.5 Configuring with STEP 7
6.5.2

Configuring with STEP 7 and S7-PCT

Configure IO device with SIMATIC Manager
1. Start the SIMATIC Manager and configure the project as described in the STEP 7 online help.
2. In the hardware catalog of HW Config, select the IO-Link master (e.g. in the distributed I/O
system ET 200SP or ET 200eco PN).
3. Drag-and-drop the IO-Link master (e.g. the 4SI SIRIUS electronics module) from the hardware
catalog to the configuration table.
4. Select the IO-Link master in the configuration table.
5. Click the right mouse button and select "Object Properties" from the shortcut
menu. Result: The "Properties" window of the IO-Link master opens.
6. On the "Addresses" tab, set the length of the inputs and the length of the outputs to 16 Bytes
and confirm with "OK".
7. Parameterize the IO-Link master.
Configuring the I/O device with the Port Configurator tool
1. In the Configuration table, select the IO-Link master (e.g. the 4SI SIRIUS electronics module).
2. Right-click and select "Launch IO-Link Configurator" in the shortcut menu. Result: S7-PCT
is started.
3. Select the SIRIUS IO-Link monitoring relay in the hardware catalog of S7-PCT.
4. Start by parameterizing the SIRIUS IO-Link monitoring relay (IO-Link device). Additional
information is available in the S7-PCT online help.
6.5.3

Configuring with STEP 7 and S7-PCT /GSD variant)

Configuring the IO-Link master in HW Config with GSD
1. Start the SIMATIC Manager and configure the project as described in the STEP 7 online help.
2. In the hardware catalog of HW Config, select the IO-Link master (e.g. in the distributed I/O
system ET 200SP or ET 200eco PN).
3. Drag-and-drop the IO-Link master from the hardware catalog to the configuration table.
4. Parameterize the IO-Link master.
Configuring the I/O device with the Port Configurator tool
1. In the Configuration table, select the IO-Link master (e.g. the 4SI SIRIUS electronics module).
2. Right-click and select "Start Device Tool" in the shortcut menu. Click on "S7-PCT" in the
submenu.
Result:S7-PCT is started.
56
3RS2 temperature monitoring relay
Equipment Manual, 02/2022, A5E42462552002A/RS-AB/002