Example: K2 alarm value at 20 °C (+ delay time):
• In the closed-circuit principle, a cable break is detected if it occurs, and the output relay is
deactivated; the display turns red
– K1 (11/12) is closed
– K2 (21/22) is closed and relay output 33/34 is open on the 3RS29
• In the open-circuit principle, a cable break is detected if it occurs, and the output relay is
deactivated; the display turns red
– K1 (11/14) is closed
– K2 (21/24) is closed and relay output 33/34 is open on the 3RS29
6.5

Configuring with STEP 7

6.5.1

Configuring with STEP 7 - prerequisites

Procedure when configuring IO-Link master and IO-Link devices
Configuration takes place in two steps with STEP 7, V5.4 SP5 or higher:
1. In HW Config, configure the IO-Link master (with GSD if necessary), e.g. the 4SI SIRIUS
electronics module or 4SI IO-Link (both require at least firmware version 1.0.1).
2. With the Port Configuration Tool S7-PCT (V2.0 or higher) you configure the connected
monitoring relay for IO-Link (IO-Link Device).
Requirements
• STEP 7 V5.4 SP5 or higher
• The Port Configurator Tool S7-PCT (V2.0 or higher) is installed on the PG/PC. You can either
install S7-PCT together with STEP 7 V5.4 SP5 or higher, or you can download it from Internet
(https://support.automation.siemens.com/WW/view/en/33102519/133100).
• The associated IO-Link IODD file (IO Device Description) is installed in S7-PCT. You can
download the IODD files for the SIRIUS Devices from Internet
support.automation.siemens.com/WW/view/en/29801139/133100).
• Optional: The GSD files are installed in HW Config. You can download the GSD files for the
ET 200SP from Internet (http://www.siemens.com/comdec).
• Optional: Install the function block FB "IOL_CALL" for backing up/restoring IO-Link master
parameters and IO-Link device parameters. You can download the function block from the
Internet. You can find more information on the function block in Chapter Module
replacement (Page 58).
3RS2 temperature monitoring relay
Equipment Manual, 02/2022, A5E42462552002A/RS-AB/002
Digital devices with IO-Link
6.5 Configuring with STEP 7