To make optimum use of available terminal space, you are advised to choose a form of crimping
that creates a corresponding rectangular contour. Trapezoidal crimping is highly suitable in this
case.
When a conductor is used that utilizes the full overall height, the terminal spring is deflected to
the maximum. It may therefore be difficult to remove this conductor because it requires further
deflection of the spring.
11.9

Connect the spring-type terminal (push-in)

Hazardous voltage
Can cause death, serious injury, or property damage.
Turn off and lock out all power supplying this device before working on this device.
The spring-type (push-in) connections allow wiring without tools for rigid conductors or
conductors equipped with end sleeves.
For wiring finely-stranded or stranded conductors without end sleeves on spring-type (push-in)
terminals, a screwdriver is required to open the spring terminal.
Tool
DIN 5264 screwdriver with size 0.5 x 3 mm (for finely-stranded conductors only). (Article
number of the screwdriver: 3RA2908-1A)
Requirements
For suitable connection cross-sections of the cables, see chapter Connection data for terminals
(Page 76).
3RS2 temperature monitoring relay
Equipment Manual, 02/2022, A5E42462552002A/RS-AB/002
WARNING
11.9 Connect the spring-type terminal (push-in)
Connection
81